Installation and operating instructions Wilo-Stratos GIGA 41
4.4.1.0 Pump name Example:
Stratos GIGA 1.5/3-165
(display in ticker format)
Only the basic pump model
appears on the display; ver-
sion names are not shown.
4.4.2.0
Software version of
user controller
Displays the software version of
the user controller.
4.4.3.0 Software version of
motor controller
Display the software version of
the motor controller
5.0.0.0 Service Service menus
5.1.0.0 Multi pump Double pump Only displayed when DP is
active (incl. sub-menus)
5.1.1.0
Operating mode Main/standby operation Only displayed in DP-MA
mode
Parallel operation Only displayed in DP-MA
mode
5.1.2.0
Setting, MA/SL Manual converting from master
to slave mode
Only displayed in DP-MA
mode
5.1.3.0
Pump cycling Only displayed in DP-MA
mode
5.1.3.1
Manual pump
cycling
Carries out pump cycling inde-
pendent of the countdown
Only displayed in DP-MA
mode
5.1.3.2
Internal/external Internal pump cycling Only displayed in DP-MA
mode
External pump cycling Only displayed in DP-MA
mode, see “AUX” terminal
5.1.3.3
Internal: Time
interval
Can be set between 8 hours and
36 hours in 4-hour increments
Displayed when internal
pump cycling is activated
5.1.4.0
Pump enabled/
disabled
Pump enabled
Pump disabled
5.1.5.0 SSM Individual fault signal Only displayed in DP-MA
mode
Collective fault signal Only displayed in DP-MA
mode
5.1.6.0
SBM Individual readiness signal Is only displayed with DP-MA
and SBM function at readi-
ness/operation
Individual run signal Only displayed in DP-MA
mode
Collective readiness signal Only displayed in DP-MA
mode
Collective run signal Only displayed in DP-MA
mode
5.1.7.0
External Off Individual external Off Only displayed in DP-MA
mode
Collective external Off Only displayed in DP-MA
mode
No. Designation Type Symbol Values/explanations Display conditions
±
±
±
±
±
±
±
±
±