User Guide
English
38 WILO SE 06/2011
The condition for hiding a menu element is explained in the last col-
umn of the table.
No. Designation Type Symbol Values/explanations Display conditions
1.0.0.0
Setpoint Setting/display of the setpoint
(for further information, see
chapter 8.6.1 “Adjusting the
setpoint” on page 34)
2.0.0.0 Control mode Setting/display of the control
mode
(for further information, see
chapters 9.4 “Setting the control
mode” on page 47 and 6.2 “Con-
trol modes” on page 13)
Constant speed control
Constant Δp-c control
Variable Δp-v control
PID control
3.0.0.0 Pump on/off ON
Pump switched on
OFF
Pump switched off
4.0.0.0 Information Information menus
4.1.0.0 Actual values Display of current actual values
4.1.1.0 Actual values sen-
sor (IN1)
Depending on current control
mode.
Δp-c, Δp-v: Value H in ft
PID control: Value in %
Not displayed for manual
control mode
4.1.2.0
Switching fre-
quency
HIGH
High switching frequency
(factory setting)
Switchover/modification
must only be carried out
when pump is at standstill
(motor not running)
MID
Medium switching frequency
LOW
Low switching frequency
4.1.3.0
Power Current power input P
1
in W
4.2.0.0 Operating data Display of operating data The operating data refer to
the module currently being
operated
4.2.1.0
Operating hours Sum of the pump's active hours
of operation (counter can be
reset by infrared interface)
±
±
±