Installation and operating instructions Wilo-Stratos GIGA 39
4.2.2.0 Consumption Energy consumption in
kWh/MWh
4.2.3.0 Countdown, pump
cycling
Time to pump cycling in h
(at a resolution of 0.1 h)
Shown only for DP-MA and
internal pump cycling. Can
be set in the service menu
<5.1.3.0>
4.2.4.0
Remaining time
until pump exercise
Time until the next pump exer-
cise (after the pump has had a 24
h standstill (e.g. via Ext. off), it
will be automatically operated
for 5 seconds)
4.2.5.0 Mains on counter Number of switching-on proce-
dures of the supply voltage
(each occasion the supply volt-
age is established after an inter-
ruption is counted)
4.2.6.0 Pump exercise
counter
Number of pump exercises car-
ried out
4.3.0.0 States
4.3.1.0 Base-load pump The value display statically
shows the identity of the regular
base-load pump.
The unit display statically shows
the identity of the temporary
regular base-load pump.
Only displayed in DP-MA
mode
4.3.2.0 SSM ON
State of the SSM relay if there is
no fault signal
OFF
State of the SSM relay if no fault
signal is present
4.3.3.0 SBM ON
State of the SBM relay if a readi-
ness/operation or “mains on”
signal is present
OFF
State of the SBM relay if no read-
iness/operation or “mains on”
signal is present
No. Designation Type Symbol Values/explanations Display conditions