User Guide

English
Installation and operating instructions Wilo-Stratos GIGA 9
5.2 Technical data
Please state all the information on the pump name plate when order-
ing spare parts.
Fluids If water/glycol mixtures are used (or fluids with a viscosity other than
that of pure water), an increase in power consumption of the pump is
to be taken into account. Only use mixtures with corrosion inhibitors.
The respective manufacturer's instructions are to be observed.
The fluid must be free of sediments.
Wilo's approval must be obtained for use of other media.
Mixtures with a proportion of glycol of > 10% influence the Δp-v
pump curve and the flow calculation.
Property Value Remarks
Speed range
500 - 5130 rpm
Depends on pump type
Nominal diameter of pipe connection 1.5/2/2.5 in
Pipe connections Flanges acc. ASME Class 125
Max. permissible liquid temperature range Water only:
from 32°F to 200°F [0°C to +90°C]
Water/glycol up to 50 %:
from -4°F to 250°F [-20°C to +120°C]
Max. permissible liquid temperature range
with high temperature seal
At 175 psi [12 bar]:
from -4°F to 250°F [-20°C to +120°C]
At 165 psi [11 bar]:
from -4°F to 285°F [-20°C to +140°C]
Ambient temperature min./max. 32°F to 104°F (0°C to +40°C)
Max. admissible operating pressure 232 psi (16 bar)
Insulation class F
Protection class Enclosure Type 5 Indoor Use Only Only for US market
IP55
Electromagnetic compatibility
Emitted interference in acc. with
Interference resistance in acc. with
EN 61800-3
EN 61800-3
Residential
Industrial
Sound pressure level
1)
< 74 dB(A)
Depends on pump type
Approved fluids Heating water
Cooling/cold water
Water/glycol mixture up to 40% vol.
Other fluids
Standard version
Standard version
Standard version
Only for special version
Electrical connection 3~380 V AC to 480 V AC ±10%,
50/60 Hz
Supported network types:
Delta, wye networks
Internal electric circuit PELV, galvanically isolated Isolated Secondary Circuit,
Limited voltage/current cir-
cuit
Speed control Built-in frequency converter
Relative humidity
- at T
environment
= 186°F (30°C)
- at T
environment
= 104°F (40°C)
90%, non-condensing
60%, non-condensing
1)
Average value of the sound-pressure level at a spatially rectangular measuring surface at a distance of 3.3 ft (1 m) from the pump surface in accordance
with ISO 3744