Specifications
TMP Oil Furnaces – Furnace Manual 
4   670-000-004/1010 
1  Check furnace location (continued) 
Air for combustion and ventilation 
Adequate combustion and ventilation air ensures 
proper combustion and reduces risk of severe 
personal injury or death from possible flue gas 
leakage and carbon monoxide emissions. 
Do not install exhaust fan in furnace room. 
Consider building construction 
Older buildings with single-pane windows, minimal weather-stripping 
and no vapor barrier often provide enough natural infiltration and 
ventilation without dedicated openings. 
New construction or remodeled buildings are most often built tighter. 
Windows and doors are weather-stripped, vapor barriers are used 
and openings in walls are caulked. As a result, such tight 
construction is unlikely to allow proper natural air infiltration and 
ventilation. 
For buildings with tight construction, provide openings directly to 
outside or to a ventilated crawl space or attic. Size the openings to 
the same specifications as for the furnace location per the following 
paragraphs. 
Follow state, provincial or local codes when sizing adequate 
combustion and ventilation air openings. In absence of codes, use 
the following guidelines when furnace is in a confined room (defined 
by NFPA 31 as less than 7200 cubic feet per 1 GPH input of all 
appliances in area. A room 8 ft. high x 30.0 ft. x 30.0 ft. is 7200 cu. 
ft.). 
Provide two permanent openings 
Openings locations 
One within 12 inches of ceiling, one within 12 inches of floor. 
Minimum height or length dimension of each rectangular opening 
should be at least 3 inches. 
When inside air is used: 
Each opening must freely connect with areas having adequate 
infiltration from outside. Each opening should be at least 140 sq. in. 
per 1 GPH input (1 sq. in. per 1000 BTU input) of all fuel-burning 
appliances plus requirements for any equipment that can pull air 
from room (including clothes dryer and fireplace). 
When outside air is used: 
Connect each opening directly, by ducts to the outdoors, or to crawl 
or attic space that freely connects with outdoors. Size per below: 
•  Through outside wall or vertical ducts – at least 35 sq. in. per 1 
GPH input (1 sq. in. per 4000 BTU input) of all fuel burning 
appliances plus requirements for any equipment that can pull air 
from room (including clothes dryer and fireplace). 
•  Through horizontal ducts – at least 70 sq. in. per 1 GPH furnace 
input (1 sq. in. per 2000 BTU input) of all fuel-burning appliances 
plus requirements for any equipment that can pull air from room 
(including clothes dryer and fireplace). 
• Where ducts are used, they should have the same cross-
sectional area as free area of openings to which they connect. 
Compensate for louver, grille or screen blockage when 
calculating free air openings. Refer to the manufacturers’ 
instructions for details. If unknown, use: 
•  Wood louvers, which provide 20-25% free air. 
•  Metal louvers or grilles, which provide 60-75% free air. 
Lock louvers in open position or interlock with equipment to 
prove open before furnace operation. 
Basement installations 
When the furnace is located in an unconfined space, such as an 
unpartitioned basement, adequate air should normally be available 
without additional openings. An unconfined space is defined as one 
having no less than 50 cubic feet room volume per 1,000 BTU/h 
input of all appliances in the space. 
If the house is of tight construction, provide air openings to the 
basement directly from outside or from a ventilated attic. Size the 
openings as described above under “When outside air is used”. 
Closet installations – special NOTICE 
Openings in closet doors 
Provide TWO openings – one within 6 inches of top of closet door, 
the other within 6 inches of the bottom of closet door. 
EACH opening must be at least 24 inches wide by 12 inches high. 
Advise homeowner that the openings to the closet 
must never be obstructed or blocked in any way. 
Failure to provide adequate air for combustion and 
ventilation could result in severe personal injury, 
death or substantial property damage. 










