Specifications
 TMP Oil Furnaces – Furnace Manual 
670-000-004/1010  3 
1  Check furnace location
Pre-installation checklist 
Verify code compliance 
  Local, state, provincial, and national codes, laws, regulations 
and ordinances 
  NFPA-31, Installation of Oil-Burning Equipment 
  National Electrical Code 
  All local codes and/or regulations take precedence over the 
instructions in this manual and should be followed accordingly. 
TMP furnaces, their burners and controls met safe 
lighting and other performance criteria when furnace 
underwent tests specified in Underwriters Laboratories 
Standard UL727. 
Check location and furnace specifications 
Use the table below to verify: 
 Furnace heating capacity 
  Space is large enough to provide required clearances 
Verify the installation will meet the requirements of this manual: 
  Clearances (page 3) 
 Combustion/ventilation air openings (pages 4) 
  Supply air duct (page 8) 
  Vent system (page 11) 
  Fuel oil piping (page 12 plus burner manual) 
  Electrical connection (page 14) 
Clearances 
Minimum clearance to combustible materials 
1.  Install the furnace, ductwork and vent such that no combustible 
surface is closer than listed in Table 1. 
Flue pipe clearances must take precedence over 
jacket clearances (listed below). 
Service accessibility clearances 
1.  Provide no less than the minimum clearances given in Table 1 to 
ensure the furnace can be properly operated, serviced and 
maintained. 
2. Always apply whichever clearance is LARGER – combustible 
construction or service accessibility. 
Flooring and foundation 
Flooring 
TMP furnaces are approved for installation on non-combustible floor. 
If a combustible floor is used, follow these instructions: 
Horizontal installation on combustible floor 
Always keep the minimum installation clearances of 1 inch between 
the combustible floor and the furnace sides. Use appropriate leveling 
legs or optional kit #HFB-1-W. 
Counterflow installation on combustible floor 
Always keep the minimum installation clearances of 1 inch between 
the combustible floor and the furnace bottom or air supply plenum. 
Use appropriate leveling base and spacers or optional kit #CFB-
1-W. 
Do not install furnace on carpeting even if foundation 
is used. Fire can result, causing severe personal 
injury, death or substantial property damage. 
Foundation 
1. Provide a solid brick or minimum 2-inch thick concrete 
foundation pad if any of the following is true: 
•  the floor can become flooded. 
•  the furnace mounting area is not level. 
Residential garage installations 
Take the following special precautions when installing the furnace in 
a residential garage. If the furnace is located in a residential garage: 
•  Mount the furnace a minimum of 18 inches above the floor 
of the garage. 
•  Locate or protect the furnace so it cannot be damaged by a 
moving vehicle. 
Table 1 Minimum clearances 
Location Application Counterflow Horizontal
Furnace 1 " 1 "
Supply plenum, warm air duct within 6ft of furnace 1 " 1 "
Back Furnace 1 " 1 "
Top Furnace casing or plenum 1 " 1 "
Bottom Furnace – combustible floor 1 " 1 "
Front Furnace 24 " 24 "
Flue pipe 18 " 18 "
* Use appropriate leveling legs or optional kit #HFB-1-W; ** Use appropriate leveling base and spacers or optional kit #CFB-1-W. 
Sides
Minimum installation clearances from combustible materials (Chimney installation)
***










