Specifications
TMP Oil Furnaces – Furnace Manual 
18 670-000-004/1010 
8  Checkout procedure 
Furnace selection 
 ..1.  Heat loss ............................... BTU/h at ............ 
o
F outdoor 
design temperature. 
 ..2. Furnace model....................................................................... 
output ..........................  BTU/h. 
 ..3. Burner model ........................................................................ 
nozzle: ............. gph ................  
o
 type............... . 
 ..4.  Burner pump pressure........................................ psig. 
Furnace installation 
 ..5.  Is furnace level? 
 ..6.  Are return and supply ducts securely attached to furnace? 
 ..7.  Are fuel filter and fuel lines installed and inspected as per 
the burner manual? 
 ..8.  Are furnace and burner wired as per the wiring diagram? 
 ..9.  120 VAC wiring: type ................  size ................ AWG. 
Vent and combustion air 
 ..10. Was existing chimney/vent system inspected and found in 
proper condition? 
 ..11. Was new vent piping installed and sealed as required? 
 ..12. Was vent sizing checked against furnace manual and 
codes? 
Ductwork 
 ..13. Was duct sizing checked against furnace manual and/or 
ACCA Manual D? 
 ..14. Were supply and return registers checked for size based on 
airflow? 
 ..15. Were balancing dampers installed as needed? 
 ..16. Was ductwork sealed and insulated as needed? 
Furnace operation 
 ..17. Is a / Are clean air filter(s) in place? 
 ..18. Was temperature rise through furnace checked (not to 
exceed 85
o
F) and blower speed adjusted if necessary? 
 ..19. Was thermostat heat anticipator set per wiring diagram? 
 ..20. Was burner started and tested per burner manual? 
 ..21. Is there proper draft and burner flame? Were final 
adjustments made with combustion test equipment? 
 ..22. Was air purged from oil piping and piping checked for leaks? 
 ..23. Was burner sealed to furnace and nuts tightened? Was 
burner harness securely plugged in? 
Obtain gas-tight seals at burner flange, cleanout 
plates and/or flue collector box to prevent possible 
flue gas leakage and carbon monoxide emissions, 
leading to severe personal injury or death. 
 ..24. Was Limit Control tested per “To start up” in this manual? 
 ..25. Was furnace cycled with thermostat? Raise to highest 
setting and verify furnace goes through normal start up 
cycle. Lower to lowest setting and verify furnace goes off. 
 ..26. Were several operating cycles observed for proper 
operation? 
 ..27. Were room thermostat(s) set to desired room temperature? 
After installation 
 ..28. Was “Installation and service certificate” (below) filled out? 
 ..29. Was Owner’s information in this manual reviewed with 
owner or maintenance person and the person instructed to 
keep the manual for future reference? 
 ..30. Were all instruction manuals placed near the furnace for 
future reference? 
Installation and service certificate 
Furnace model__________________________________________________  Series _______________________  
Serial number_______________________________________Date installed_____________________________  
 
Installation instructions have been followed. 
  Checkout sequence has been performed. 
  Above information is certified to be correct. 
  Information received and left with owner/maintenance person. 
Installer ______________________  ________________________  _____________________ 
 (company)  (address)  (phone) 
  ________________________________________________  
  (installer’s signature) 