Specifications
 TMP Oil Furnaces – Furnace Manual 
670-000-004/1010  17 
Gasket for overfire 
pressure reading 
7  Start up 
Follow information below to prevent severe personal 
injury, death or substantial property damage: 
•  Do not use gasoline, crankcase drainings or any oil 
containing gasoline. See burner manual for proper 
fuel oil. 
•  Do not attempt to start burner when excess oil has 
accumulated, when unit is full of vapor or when 
combustion chamber is very hot. 
•  Do not start burner unless collector box, venting and 
burner mounting plate are secured in place. 
•  Never burn garbage or paper in the furnace. 
•  Never leave combustible material around it. 
To start furnace 
1.  Factory burner adjustment and settings may not be suitable for 
specific job conditions. Refer to burner manual for burner start 
up, adjustment and checkout procedures. 
2.  Set room thermostat to call for heat. 
3.  Start burner as described in burner manual. 
4.  The furnace blower will delay for a short time after burner starts, 
until the Limit/Fan switch senses air temperature above the fan 
ON setting. 
5.  Set room thermostat to its lowest setting. Burner should turn off. 
6.  Furnace blower will continue to run until the Limit/Fan switch 
senses air temperature below the fan OFF setting. 
7.  Set the room thermostat to call for heat again. Allow furnace to 
heat to design temperature. Then adjust burner for correct 
combustion, using combustion test equipment. Adjust burner for: 
Draft: -0.00” to +0.035” water column draft in furnace 
combustion chamber. 
For pressure reading, replace the sight glass by the gasket 
supply with the appliance. 
After  the  verification,  put  back  in  place  the  sight  glass. 
See Figure 3. 
CO
2
: between 10% and 11½ %, with 0 smoke. 
To start furnace (continued) 
Make final burner adjustments using combustion test 
equipment to assure proper operation. 
8.  Check furnace and duct system for proper operation and 
conditions. 
9.  Inspect vent system for proper operation. 
10. To set Limit/Fan switch: 
The blower operates until the air temperature drops below the 
fan OFF setting. If the air at the supply registers is too warm at 
blower start up or shutdown, lower the fan OFF and ON settings 
on the Limit/Fan switch. 
To check operation of the limit switch, slide a piece of cardboard 
into the furnace filter slot. After a few minutes of operation (not 
more than 5 minutes), the burner should shut off (limit switch 
open). The blower will operate until the furnace cools down. 
Remove cardboard when finished. 
11. Perform complete test of the burner cad cell control as per the  
burner manual instructions. 
To shut down furnace 
1.  Set the room thermostat to its lowest setting. 
2.  Turn off the disconnect switch on the 120-VAC power line to the 
furnace. 
3.  If the burner will be shut down for an extended time, tightly close 
all oil valves. 
4.  Refer to burner manual for any additional instructions. 
Figure 6 
DNS-1092 Rev. A 