Specifications
TMP Oil Furnaces – Furnace Manual 
14 670-000-004/1010 
6  Wire furnace & burner 
Electric shock hazard. It can cause severe personal injury or death if power source, including the service switch on the 
furnace, is not disconnected before installation or servicing.
Wire burner 
The burner harness is factory-wired to the furnace. Plug the burner 
harness into the matching burner connector. Refer to the wiring 
diagrams on pages 15 and 16 for further information. 
Install and wire thermostat 
Locate the room thermostat on an interior wall in the natural 
circulating path of room air. Do not locate thermostat so it is exposed 
to cold air infiltration, drafts from windows or doors, air currents from 
supply or return air registers, behind obstructions, on a shelf, in a 
closet, or in a corner. 
Ensure the thermostat won’t be exposed to heat from nearby 
fireplace, radio, television, lamp or rays from the sun. Do not mount 
thermostat on a wall over a supply or return duct, chimney or vent. 
Wire thermostat to furnace and set thermostad anticipator as shown 
on wiring diagram, pages 15 and 16. 
Figure 3 
Blocked Vent Shut-Off device wiring 
(Optional) 
1.  Blocked Vent Shutt-Off device (BVSO) 
2.  Electrical kit supplied. 
3.  Connect one red wire to limit switch. 
4.  Disconnect red wire from limit switch and connect to one red 
wire from BVSO. 
5.  Connect the green ground wire to a cabinet screw. 
Connect power wiring 
All wiring must conform to: 
•  National Electrical Code, ANSI/NFPA 70, latest edition and any 
additional national, state or local codes. 
•  In Canada, CSA C22.1 Canadian Electrical Code Part One and 
any local codes. 
•  Wiring must be N.E.C. Class 1. If original wire, as supplied with 
furnace, must be replaced, type 105
o
C wire or equivalent must 
be used. Supply wiring to furnace and additional control wiring 
must be 14 gauge or heavier. 
•  Provide electrical ground at furnace as required by codes. 
Connect 120 VAC/60 Hertz, single phase separate electrical line 
from the main house panel to the power leads in the external 
junction box as shown on wiring diagrams on pages 15 and 16. 
Provide a fused disconnect in the power wiring, following all local 
codes. 
Ensure the wire size and type are adequate for the electrical load 
(see Section 12 and furnace nameplate for value). 
Limit control 
The furnace is equipped with a fan switch/limit control. This control 
limits the air leaving the heat exchanger to 200
o
F or less. The fan 
switch continues fan operation until the air drops to a preset 
temperature. For most installations, set the blower ON setting at 
130
o
F and blower OFF setting at 90
o
F. If a longer cool down period 
is desired, lower the OFF setting. 
Counterflow furnaces also contain an automatic reset auxiliary limit 
control to prevent blower motor and filters from being overheated. 