Operating instructions Digital indicator model DI30 14037419 • V2.
GB Operating instructions model DI30 page 1 - 40 © 2010 WIKA Alexander Wiegand SE & Co. KG All rights reserved. WIKA® is a registered trademark in various countries.
Contents 1 2 General information ................................................................................4 Safety .......................................................................................................5 2.1 2.2 2.3 2.4 3 4 Intended use........................................................................................5 Personnel qualification.........................................................................7 Special hazards ..............................................
1 General information 1 General information The instrument described in the operating instructions has been designed and manufactured using state-of-the-art technology. All components are subject to stringent quality and environmental criteria during production. Our management systems are certified to ISO 9001. These operating instructions contain important information on handling the instrument. Working safely requires that all safety instructions and work instructions are observed.
2 Safety Explanation of symbols WARNING! ... indicates a potentially dangerous situation that can result in serious injury or death, if not avoided. Information ... points out useful tips, recommendations and information for efficient and trouble-free operation. DANGER! ...identifies hazards caused by electric power. Should the safety instructions not be observed, there is a risk of serious or fatal injury.
2 Safety Please read the following safety advice and the assembly before installation and keep it for future reference. If the instrument is transported from a cold into a warm environment, the formation of condensation may result in the instrument malfunctioning. Before putting it back into operation, wait for the instrument temperature and the room temperature to equalise. Notes on installation There must be no magnetic or electric fields in the vicinity of the device, e.g.
2 Safety 2.2 Personnel qualification WARNING! Risk of injury should qualification be insufficient! Improper handling can result in considerable injury and damage to equipment. The activities described in these operating instructions may only be carried out by skilled personnel who have the qualifications described below. Keep unqualified personnel away from hazardous areas.
2 Safety 2.4 Labelling / Safety marks Product label 1: power supply 2: order code 3: serial no. 4: CE mark 5: product name 6: connection diagram Explanation of symbols Before mounting and commissioning the instrument, ensure you read the operating instructions! CE, Communauté Européenne Instruments bearing this mark comply with the relevant European directives.
3 Specifications 3 Specifications Specifications Display Principle Character size Indication range Indication time Memory Input Number and type Input signal Input configuration Accuracy Temperature drift Measuring principle Resolution Measuring time Transmitter supply Power supply Power consumption Electrical connection Alarm output Number and type Contact Switching cycles 7-Segment-LED, red, 4 digit 20 mm -999 … +9999 0.1….
3 Specifications Case Material Ingress protection Dimensions Mounting clearance Weight Mounting {Wall mounting enclosure} Material Ingress protection Dimensions Cable gland Mounting Aluminium, black Front: IP 54, Rear: IP 00 96 x 96 x76 mm (w x h x d) including terminals horizontal 120 mm / vertical 120 mm (recommended) Approx. 530 g sliding fasteners, fixed via screws, for panel thicknesses from 1 mm to 10 mm ABS, black, cable gland IP 65 160 x 130 x 60 mm (w x h x d) Cable thickness: 4.0...8.
4 Design and function Operating elements 1: Program key 2: DOWN key 3: UP key 4: Zero key 5: 7 segment display 6 +7: LEDs for displaying the alarm contacts 4 Design and function 4.1 Short description With the digital indicator DI30 standard signals DC 0/4…20 mA or DC 0…5/10 V can be measured. The 4 digit display shows the measurements or the scaled value of the measurement. During programming the display is used to indicate the set values and the user prompts.
5 Transport, packaging and storage 4.2 Scope of delivery The scope of delivery is: Indicator for panel mounting: Indicator 2 fixing elements Seal Operating instructions Indicator for wall mounting: Indicator Operating instructions Cross-check scope of delivery with delivery note. 5 Transport, packaging and storage 5.1 Transport Check instrument for any damage that may have been caused by transport. Obvious damage must be reported immediately. 5.
6 Commissoning, operation Store the instrument in its original packaging in a location that fulfils the conditions listed above. If the original packaging is not available, pack and store the instrument as described below: 1. Wrap the instrument in an antistatic plastic film. 2. Place the instrument, along with shock-absorbent material, in the packaging. 3. If stored for a prolonged period of time (more than 30 days), place a bag, containing a desiccant, inside the packaging.
6 Commissoning, operation 1. After removing the fixing elements, insert the device. 2. Check the seal to make sure it fits securely. 3. Click the fixing elements back into place and tighten the clamping screws by hand. Then use a screwdriver to tighten them another half a turn. CAUTION! The torque should not exceed 0.1 Nm! Indicator for wall mounting: The wall-type housing consists of an upper part and a lower part. A suitable seal has been inserted in the lower part to achieve protection IP 66.
6 Commissoning, operation 1. The cover flaps have to be opened on the right and left side. Loose the four fixing screws, which connect the upper and lower part of the enclosure, with a screw driver. Remove the upper part. 2. Fasten the enclosure to the wall. 3. Connecting cables have to be fed into the enclosure via the PG screws. 4. After connection the upper part of DI30 will be placed on the lower part. Using the four fixing screws, screw the upper part to the lower part.
6 Commissoning, operation 6.2 Electrical connection All the necessary signals for operation are connected to the rear terminals. The connecting terminals are designed as removable screw-type terminals with a grid pitch of 5.08 mm. This makes it possible to connect wires of up to 2.5 mm². 6.2.
6 Commissoning, operation Transmitter supply The DC 24 V transmitter supply is available at terminals 13 and 14. The transmitter supply is galvanic insulated from the measuring input. Current loop sensors (2-wire) and 3-wire and 4-wire sensors can be operated via the transmitter supply as long as their current consumption is not higher than 50 mA (Power consumption < 1.2 VA). Transmitter supply 13 Transmitter supply (-) 14 Transmitter supply (+) 6.2.
6 Commissoning, operation c) 0…5 V/0…10 V signal, 3-wire-transmitter The ground is bridged via the sensor, which eliminates the measuring error through the drop in voltage on the transmitter supply wires.
6 Commissoning, operation 6.3 Function and operation description 6.3.1 Operation The DI30 has 4 keys ([P], [], [], [O]), with which you can parameterise and call up various functions during operation. Additionally it has a 4-digit 7-segment display and two LEDs for displaying the alarm contacts.
6 Commissoning, operation 6.3.2 Switching on Before switching on you have to check all the electrical connections to make sure they are correct. On completion of the installation, the device can be switched on by applying the power supply. During the switching-on process a segment test is performed for approx. 1 second, whereby all LEDs on the front (including alarm LEDs) are triggered. After this, the type of software is indicated for approx. 1 second and then, also for 1 second, the software version.
6 Commissoning, operation 6.3.4 Description of the alarm outputs With the aid of the LEDs below the 7-segment display, you can view the switching state of the alarm outputs. An active relay is indicated by the relevant LED lighting up.
6 Commissoning, operation Switch-on delay The relay is on e.g. 10 seconds after reaching the threshold. Briefly exceeding the threshold does not lead to the relay being switched on. The switch-off delay functions in a similar manner, in other words it keeps the alarm output switched on until the parameterised time has elapsed. Optical response: display flashing The switching on of one or more alarm outputs can also be set to trigger a flashing of the display, to enhance the optical response. 6.
6 Commissoning, operation Changing to other program numbers To change between individual program numbers, hold the [P] key down and press the [] key for changing to a higher program number or the [] key for changing to a lower number. By keeping the keys pushed, e.g. [P] & [], the display will begin, after approx. 1 second, to automatically run through the program numbers. Example: Under PN0 a 1 is parameterized. Hold the [P] key down and press the [] key once. PN1 appears in the display.
6 Commissoning, operation Saving parameters All parameters must be acknowledged by the user by pressing the [P] key for one second. The changed parameters are then taken over as the current operating parameters and saved in the EEPROM. This is confirmed by horizontal bars lighting up in the display. Example: Save the parameters by pressing [P] for one second. All the newly entered data are confirmed by the unit. If no confirmation is received, the relevant parameters have not been saved.
6 Commissoning, operation Sensor linearisation In addition, non-linear sensors can be linearised with the aid of a characteristic line that can be saved in the indicator. This is described with the following example: The sensor signal must be parameterised in a strictly monotonously manner, i.e. every new calibration point (e.g. PN104) must have a higher input signal than the previous one (e.g. PN103) so that it is taken over by the indicator. Otherwise, no confirmation will be shown.
6 Commissoning, operation 6.6 Description of device parameters The DI30 has a number of unit parameters with which the function of the indicator can be adjusted to the relevant measuring tasks. Because of the large number of these settings and the limited possibility of displaying them on the 7-segment display, the parameters have been given consecutive numbers. (see chapter “6.
6 Commissoning, operation PN13: Indication time The indication time is the interval at which the display is updated. The longer the time between two indication cycles, the more calm the display. As a rule, the eye perceives the indication time of 1 sec. as very pleasant. If the adjusted indication time is longer than the adjusted measuring time (PN14), no averaging of the detected measuring values during the display time takes place.
6 Commissoning, operation To activate the set user level, you must enter a 4-digit number under PN51 as a “locking code” and confirm it by pressing the [P] key for approx. 1 second. On changing to programming mode, the unit jumps to the first authorised program number. If user level PN52 = 3, then, for example, the parameters of the alarm outputs can be changed, but changing the parameter of the measuring input (PN0) is not possible at this user level.
6 Commissoning, operation PN100 to PN110: Linearisation Through linearisation, the user has the possibility to linearise a non-linear sensor signal. A detailed description can be found in the chapter on Sensor linearisation. Under PN100, the desired number of additional set points can be released. Only after changing the number are they accessible via the configuration PN101 to max. PN110. If PN100 = 0, then no PN101 will be displayed.
6 Commissoning, operation 6.7 Program number table The program table lists all the program numbers (PN) with their function, range of values, default values and user level. PN Function Range of value 0 Measuring input Current, Voltage: 0 = Sensor calibration 1 = 0 ... 20 mA 2 = 4 ... 20 mA 3 = 0 ... 10 V 4 = 0 ... 5 V -999 ... 9999 -999 ... 9999 0=0 1 = 0.0 2 = 0.00 3 = 0.000 -999 … 9999 Parameters 1 to 4 make use of the factory calibration.
6 Commissoning, operation PN Function Alarm output 1 60 Alarm output 1 61 62 63 64 65 Threshold Hysteresis Active below / above threshold value Switch delay Delay type Alarm output 2 70 Alarm output 2 71 72 73 74 75 Threshold Hysteresis Active below / above threshold value Switch delay Delay type Linearisation 100 Number of additional setpoints 101... Setpoints 1 ... 10 110 Information 200 Serial number Range of value Default User level 0 = deactivated 1 = activated -999 ... 9999 1 ...
7 Maintenance and cleaning 6.8 Default values Reset to default values To return the unit to a defined basic state, a reset can be carried out to the default values. The following procedure should be used: Switch off the power supply Press button [P] Switch on the power supply and press [P] for further approx. 2 seconds until „- - - -“ is shown in the display. With reset, the default values of the program table are loaded and used for subsequent operation.
8 Faults 8 Faults Fault The unit permanently indicates overflow „ ¯ ¯ ¯ ¯ “ (4 bars in the upper part of the display) The unit permanently indicates underflow „ _ _ _ _ “. (4 bars in the lower part of the display) The device shows “HELP” in the 7segment display. Program numbers for parameterising the input are not available. „Err1“ lights up in the 7-segment display Solution The input has a very high measurement, check the measuring circuit.
9 Dismounting, return and disposal 9 Dismounting, return and disposal WARNING! Residual media in dismounted instruments can result in a risk to persons, the environment and equipment. Take sufficient precautionary measures. 9.1 Dismounting To dismount the instrument, do the following steps: Indicator for panel mounting: 1. Open the clamping screws and remove the fixing elements. 2. Remove the instrument and seal from panel cutout.
9 Dismounting, return and disposal 9.3 Disposal Incorrect disposal can put the environment at risk. Dispose of instrument components and packaging materials in an environmentally compatible way and in accordance with the country-specific waste disposal regulations.
10 Application example: DI30 and gas cylinder scale GCS-1 10 Application example: DI30 and gas cylinder scale GCS-1 Adjustment hints for digital indicator DI30 in combination with gas cylinder scale GCS-1 In the following there is an example explaining the setting parameters of DI30. With the help of the gas cylinder scale GCS-1 the level of a gas cylinder has to be calculated. This value shall be displayed on DI30. At a certain level, an alarm will be triggered.
10 Application example: DI30 and gas cylinder scale GCS-1 Adjustment With the program numbers 0, 1, 2 and 3 the indicator is configured according to the connected scale. For program number 5 „Offset shift on display value“ the TARA-value has to be entered as negative value. The weight of the scale is subtracted automatically, only the actual weight of the filling will be shown in the display.
11 Appendix: Declaration of conformity 11 Appendix: Declaration of conformity 38 WIKA operating instructions digital indicator DI30
11 Appendix: Declaration of conformity WIKA operating instructions digital indicator model DI30 39
WIKA global WIKA subsidiaries worldwide can be found online at www.wika.com. WIKA Alexander Wiegand SE & Co. KG Alexander-Wiegand-Straße 30 63911 Klingenberg • Germany Tel. (+49) 9372/132-0 Fax (+49) 9372/132-406 E-Mail info@wika.de www.wika.