User Manual

Operating Instructions Temperature Indicating Controller CS4R
V1.2
05/2006 - 4 -
1. Model Name and Order Code
CS4R - 3 E - / M - - - Series name: CS4R
Control action 3 PID
(1)
Alarm output 1 E alarm action is selectable by key operation
(2)
R
relay
S
logic level DC 0/12 V for solid state relay
Control output
A
analogue current signal (4 ... 20 mA)
(3)
Multi-function input
M settable input configuration
(4)
H AC 100 ... 240 V, 50 ... 60 Hz
Power supply
L AC/DC 24 V
Z
without
Digital interface
5
RS485
ZZZ without
W10 single phase system (max. 5 A)
W11 single phase system (max. 10 A)
W12 single phase system (max. 20 A)
Heater burnout Alarm
W15 single phase system (max. 50 A)
Z without
Necessary accessory for current input
R shunt resistor 50 Ω
B factory adjustment
Instrument configuration
K to customer specification
Z without
Additional order info
T additional text
(1) PID, PI, PD, P and ON/OFF action are programmable.
(2) Alarm action (9 types and no alarm) and Energized/Deenergized are selectable by key operation.
(3) The controller with control output analogue current signal (4 … 20 mA) can be configured for use as
temperature transmitter.
(4) Thermocouple, RTD, DC current and DC voltage are selectable by key operation.