User Manual

Operating Instructions Temperature Indicating Controller CS4R
V1.2
05/2006 - 30 -
12. Character table (to copy and complete for your documentation)
[Main setting mode]
Character Setting item Default value Data
Set value 0 °C
[Sub setting mode]
Character Setting item Default value Data
AT Auto-Tuning cancellation
OUT proportional band setting 2.5 %
Integral time 200 s
Derivate time setting 50 s
ARW setting 50 %
OUT proportional cycle setting 30 s or 3 s
Manual reset setting 0.0
Alarm setting 0 °C
Heater burnout alarm setting 0.0 A
Loop break alarm action time setting 0 min
Loop break alarm action span setting 0 °C
[Auxiliary function setting mode 1]
Character Setting item Default value Data
Setting value lock selection Unlock
Sensor correction setting 0.0 °C
Communication protocol selection WIKA protocol
Instrument number setting 0
Data transfer rate selection 9600 bps
Parity selection Even
Stop bit selection 1
[Auxiliary function setting mode 2]
Character Setting item Default value Data
Input type selection K: –200 ... +1370 °C
Scaling high limit setting 1370
Scaling low limit setting –200
Decimal point place selection no decimal point
PV filter time constant setting 0.0 s
OUT high limit setting 100 %
OUT low limit setting 0 %
OUT ON/OFF action hysteresis 1.0 °C
Alarm action selection no alarm action
Alarm action Energized/Deenergized energized
Alarm HOLD function selection not used
Alarm hysteresis setting 1.0 °C
Alarm action delayed timer setting 0 s
Direct/Reverse action selection Reverse (heating) action
AT bias setting 20 °C
SVTC bias setting 0
Controller/converter function selection controller function
Output status selection when input burnout output OFF