Owner manual

Operating Instructions Temperature Indicating Controller CS4H / CS4L
V1.1
05/2006 - 19 -
5.2 Main setting mode
If the MODE key is pressed, main setting mode is selected.
The setting value (numeric value) can be increased or decreased by pressing the
or key.
If the MODE key is pressed, the setting value is registered and the controller will revert to the PV/SV
display mode.
SV1 [ ]
• Sets SV1.
• Setting range: SV low limit to SV high limit or
Scaling low limit value to Scaling high limit value
• Default: 0 °C
SV2 [ ]
• Sets SV2.
• Setting range: SV low limit to SV high limit or
Scaling low limit value to Scaling high limit value
• Default: 0 °C
5.3 Sub setting mode
By pressing the MODE key while holding down the
key, Sub setting mode can be selected.
The or key increases or decreases the setting value (numeric value).
By pressing the MODE key, setting value is registered and the next setting item is selected.
AT setting/ Auto-reset setting [ / ]
• Sets AT (Auto-tuning) or Auto-reset (offset correction).
Auto-reset can be performed only during PD and P action.
(Not available for PID, PI and ON/OFF action)
• Default: Both Auto-tuning and Auto-reset Cancellation
[Auto-tuning]
• If the auto-tuning performance is designated, AT indicator blinks and the controller reverts to the
PV/SV display mode.
After auto-tuning ends, AT indicator is turned off and P, I, D and ARW values are automatically
set.
• During auto-tuning, none of the settings can be performed.
• If the auto-tuning is released during the process, P, I, D and ARW values revert to their former
value.
• If the
OUT
/
OFF
key is pressed during auto-tuning, control output OFF function is activated, and if the
OUT
/
OFF
key is pressed again, PID auto-tuning is cancelled.
[Auto-reset]
• If the auto-reset is performed, offset correction immediately starts and the controller reverts to
the PV/SV display mode. (The corrected value is automatically set and AT indicator blinks)
• During 4 minutes of auto-reset performing, other settings cannot be performed to prevent key
misoperations.
After auto-reset ends, AT indicator is turned off and all settings can be carried out.
OUT1 proportional band setting [ ]
• Sets OUT1 proportional band.
ON/OFF action when set to 0 or 0.0.
• Setting range: 0 … 1000 °C (0 … 2000 °F)
With a decimal point: 0.0 … 999.9 °C (0.0 … 999.9 °F)
DC input: 0.0 … 100.0 %
• Default: 10 °C
OUT2 proportional band setting [ ]
• Sets OUT2 proportional band.
ON/OFF action when set to 0 or 0.0.
• Not available when 2. control output (option) is not applied or when OUT1 is ON/OFF action
• Setting range: 0.0 … 10.0 times (multiplying factor to OUT1 proportional band)
• Default: 1.0 times