The following items can be designated by the DIP switch (SW304).
Factory adjusted as all switches OFF [
].
[Table 3.2-1]
Item
Sw. No.
Designation Switch status
Fuzzy self-tuning PID action No.1: OFF No.2: OFF
PID action No.1: ON No.2: OFF
PD action No.1: OFF No.2: ON
Control action
1
and
2
ON/OFF action No.1: ON No.2: ON
Heating (reverse) action No.3: OFFHeating/Cooling
action
3
Cooling (direct) action No.3: ON
No standby action No.4: OFFAlarm 1 (A1)
standby action
4
Standby action No.4: ON
No standby action No.5: OFFAlarm 2 (A2)
standby action
(*1)
5
Standby action No.5: ON
°C No.6: OFF
°C/°F 6
°F No.6: ON
K, J, R, B, N, PL- ,
Pt100, JPt100
(With decimal point)
No.7: OFF
Sensor input
(*2)
7
S, E, T, C,
Pt100 (Without decimal point)
No.7: ON
Manual start No.8: OFFProgram start
Auto/Manual
8
Automatic start No.8: ON
*1: The standby function will not work if the option A2 is not applied.
*2: The sensor input can be designated by the combination of this item and the rotary
switch sensor input (SW303). (See page 11.)
Program start: This item is available for the program control.
Manual start : Program starts by pressing the
key.
Automatic start : Set program is automatically started from step 1 by turning the power
supply to the instrument on (after 2 seconds of warm-up status).