User Manual

Operating Instructions Temperature Indicating Controller CF2S
V1.2
08/2004 - 39 -
+2
0
12. Specifications
12.1 Standard specifications
Mounting method : Flush
Setting : Input system using membrane sheet key
Display
PV display : Red LED display 4 digits, size: 8(H) x 4(W)mm
SV/MV/TIME display : Green LED display 4 digits, size: 8(H) x 4(W)mm
Indicating accuracy
Thermocouple input : Within ±0.3% of input range full scale ±1digit
however, for R or S input, the range 0 to 200°C (400°F), within ±6°C (12°F)
When B input, the range 0 to 300°C (600°F), accuracy is not guaranteed.
When K, J, T input, the range less than 0°C (32°F),
within ±0.5% of full scale ±1digit
(Cold junction compensating accuracy, ±1°C, at 0 to 50°C)
RTD input : Within ±0.3% of input range full scale ±1digit
Setting accuracy : The same as indicating accuracy
Input sampling period : 0.125 seconds
Input
Thermocouple : K, J, R, S, B, E, T [JIS, IEC], C (W/Re5-26) [ASTM],
N (IEC) and PL-ll (NBS)
External resistance, 100 or less
In the case of input burnout, Upscale
RTD : Pt100 (JIS, IEC), JPt100, 3-wire system
Allowable input lead wire resistance 10 or less per wire
In the case of input burnout, Upscale
Control output
Relay contact : 1a
Control capacity, 250Vac 3A (resistive load)
250Vac 1A (inductive load cosø=0.4)
Non-contact voltage : For SSR drive
12 VDC maximum 40mA DC (short circuit protected)
Current : 4 to 20mA DC (Isolated type)
Load resistance, maximum 550