User Manual
Operating Instructions Temperature Indicating Controller CF1H
V 1.2
•
01/2007 - 32 -
Display selection when Mode to select the display when the control output is off.
control output is off
Selection [Factory adjusted as indicating OFF on the PV display]
MODE
OFF is indicated on the PV display.
No indication (all unlit).
Only PV is indicated.
Main setting value Mode to set the rising rate of the main setting
rising rate setting value. (Rising value per minute)
Setting value Setting the value to 0 or 0.0 disables the function.
MODE Setting range:
0 … 9999 °C/min. Thermocouple, except T and RTD without
a decimal point
0.0 … 999.9 °C/min. Thermocouple T and RTD with
a decimal point
0 … 9999, DC input (Decimal point place follows
the selection.)
[Factory adjusted as 0°C/min.]
Main setting value Mode to set the falling rate of the main setting
falling rate setting value. (Falling value per minute)
Setting value Setting the value to 0 or 0.0 disables the function.
MODE Setting range:
0 … 9999 °C/min. Thermocouple, except T and RTD without
a decimal point
0.0 … 999.9 °C/min. Thermocouple T and RTD with
a decimal point
0 … 9999 DC input (Decimal point place follows
the selection.)
[Factory adjusted as 0 °C/min.]