Cooling action mode selection Mode to select the Cooling action,
Selection Air cooling, Oil cooling or Water cooling.
[Factory adjusted as Air cooling]
MODE This display is indicated only when the option [D 2]
is applied.
Air cooling (linear characteristic)
Oil cooling (The 1.5th power of Air cooling characteristic)
Water cooling (The 2nd power of Air cooling characteristic)
Cooling output Mode to set high limit value of the cooling output.
high limit setting Setting range:
Setting value Cooling output low limit value to 105 %
Setting greater than 100 % is effective to the type
MODE Current output.
[Factory adjusted as 100 %]
This display is not indicated when the option [D 2]
is not applied, or when ON/OFF action of cooling side.
Cooling output Mode to set the low limit value of the cooling output.
low limit setting Setting range: –5 % to cooling output high limit value
Setting value Setting less than 0 % is effective to the type Current output.
[Factory adjusted as 0 %]
MODE This display is not indicated when the option [D 2]
is not applied or when ON/OFF action of cooling side.
Cooling output ON/OFF Mode to set the ON/OFF action hysteresis of the
action hysteresis setting cooling control output.
Setting value Setting range: 0.1 … 100.0 °C
[Factory adjusted as 1.0 °C]
MODE This display is indicated when the ON/OFF action is
designated in Control action designation and when the
option [D 2] is applied.