User Manual
Operating Instructions Temperature Indicating Controller CF1H
V 1.2
•
01/2007 - 23 -
As to the Lock mode 3
When using the CF1H as a Fixed value controller.
The setting values can temporarily be changed by the selected
setting value memory number, however, when the number is
changed, the setting values changed by the previous number are
canceled and returns to the former values.
When using the CF1H as a Program controller.
The setting values can temporarily be changed by the step
number performing, however, when the step number is changed,
the setting values are canceled and returns to the former values.
Setting value change is null when the controller is waiting for
running. The running starts by the values memorized.
Main setting value Mode to set the high limit of main setting value.
high limit setting (If scaling high limit value is changed,
Setting value this setting value will be changed as well.)
Setting range: Main setting value low limit to
MODE scaling high limit value
(The decimal point place follows the selection.)
[Factory adjusted as 400 °C]
Main setting value Mode to set the low limit of main setting value.
low limit setting (If scaling low limit value is changed,
Setting value this setting value will be changed as well.)
Setting range: Scaling low limit value to
MODE main setting value high limit
(The decimal point place follows the selection.)
[Factory adjusted as 0 °C]
Sensor correction setting Mode to set the correct value of the sensor.
Setting value Setting range: –100.0 … 100.0 °C
[Factory adjusted as 0.0 °C]
MODE