Operating Instructions Temperature Indicating Controller CF1H ***** Note to users ***** Before operating this controller, make sure you have understood the following. Warning Turn the power supply to the instrument OFF before wiring or checking. Working or touching the terminal with the power switched ON may result in Electric Shock, which can cause severe injury or death. Moreover, the instrument must be grounded before the power supply to the instrument is turned on.
Operating Instructions Temperature Indicating Controller CF1H --- CONTENTS --1 Model names ---------------------------------------------------------------------------------------------------2 Name and functions of the sections 6 2.1 Names and displays ---------------------------------------------------------------------------------------2.2 Keys ------------------------------------------------------------------------------------------------------------ 7 8 3 Setup 3.
Operating Instructions Temperature Indicating Controller CF1H (5) Auxiliary function setting mode 2 Scaling high limit value setting ----------------------------------------------------------------------Scaling low limit value setting -----------------------------------------------------------------------Decimal point place selection -----------------------------------------------------------------------PV filter time constant setting -----------------------------------------------------------------------Ma
Operating Instructions Temperature Indicating Controller CF1H 7 Action explanations 7.1 Standard action drawings --------------------------------------------------------------------------------7.2 Heater burnout alarm action drawing -----------------------------------------------------------------7.3 ON/OFF action drawings ---------------------------------------------------------------------------------7.
Operating Instructions Temperature Indicating Controller CF1H 1. Model names CF1H -3 3 Alarm Output A- / M- - - - ..... A R S A Input Power supply Mounting provision M H L FT FS Instrument configuration B ?/# Options 2AS (3) 2AR (3) 2AL (3) DR2 (4) DS2 (4) DA2 (4) TA4 (5) TV1 (5) W12 (6) W15 (6) W32 (6) W35 (6) CR2 (7) CR5 (7) EA0 (8) EA4 (8) EV0 (8) EV1 (8) SM7 KAB IP4 (9) P24 (1) (2) (3) - (8) (9) V 1.
Operating Instructions Temperature Indicating Controller CF1H 2 Name and functions of the sections 2.1 Names and Displays (4) (1) (5) (2) (6) (3) (11) (12) (7) (13) (8) (14) (9) CF1H (10) c^ p q jlab lrq lcc AUTO MAN (15) (16) (17) [Fig. 2.1-1] (1) PV display Indicates the Process variable (PV) with red LED. (2) SV display Indicates the Setting value (SV), Manipulating value (MV) or Time (TIME) with green LED.
Operating Instructions Temperature Indicating Controller CF1H (10) Serial communication output indicator (TX/RX) [Option] The green LED is lit when transmitting serial communication TX. (11) Alarm 1 (A1) output action or Pattern end 1 output indicator (A1) The red LED is lit when the Alarm 1 (A1) output or Pattern end (A1) output is on. (12) Alarm 2 (A2) output action or Pattern end 2 output indicator (A2) [Option] The red LED is lit when the Alarm 2 (A2) output or Pattern end 2 output is on.
Operating Instructions Temperature Indicating Controller CF1H 3. Setup 3.1 Taking the internal assembly out Before the power supplied to this instrument is on, take the internal assembly out from the case by pushing the hook (bottom of the instrument) in the direction indicated by the arrow and holding the notches. [Fig. 3.1-1] Warning Do not take the inner assembly out nor touch the terminal with the power supply on.
Operating Instructions Temperature Indicating Controller CF1H The following items can be designated by the DIP switch (SW304). Factory adjusted as all switches OFF [ ]. [Table 3.2-1] Item Control action Sw. No.
Operating Instructions Temperature Indicating Controller CF1H Select the sensor type by rotary switch sensor input (SW303). Factory adjusted as K, [ ]. [Table 3.2-2] Rotary Sw. No. V 1.2 • DIP Sw. No. 7 Type of sensor 0 OFF K -200 to 1370°C -320 to 2500°F 1 OFF J -200 to 1000°C -320 to 1800°F 2 OFF R 0 to 1760°C 0 to 3200°F 3 OFF B 0 to 1820°C 0 to 3300°F 4 OFF PL-ll 0 to 1390°C 0 to 2500°F 5 OFF N 0 to 1300°C 0 to 2300°F 6 OFF Pt100 -199.9 to 850.0°C -199.9 to 999.
Operating Instructions Temperature Indicating Controller CF1H The alarm action type and the pattern end output when program control can be designated by the rotary switch A1 (SW302) and A2 (SW301). The rotary switch A2 (SW301) is equipped only when the option A2 is applied. Rotary switch A1 (SW302): Alarm 1 (A1) action or Pattern end 1 output. Rotary switch A2 (SW301): Alarm 2 (A2) action or Pattern end 2 output. Factory adjusted as No alarm action, [ ]. [Table 3.2-3] Alarm 1 action A1 Rotary Sw.
Operating Instructions Temperature Indicating Controller CF1H 4 Operations 4.1 Operating flow chart Instrument power ON Warm-up status (For approx. 2s, displays as shown on page 18.) OUT/ OFF PV/SV display mode 1s Control output OFF function Manual control AUTO/ MAN MODE 3s Output manipulating value MODE MODE Step rest time *1 MO + MODE MODE [Main setting mode] [Sub setting mode] Main setting PV MODE *2 Setting value memory No.
Operating Instructions Temperature Indicating Controller CF1H : Options + MODE : Press the MODE key while the key is being pressed. + MODE 3s: Press the MODE key for approx. 3 seconds while the key is being pressed. + + MODE 3s: Press the MODE key for approx. 3 seconds while the and keys are being pressed. + 3s : Pressing the key, press the key for approx. 3 seconds. *1: Step rest time is indicated only during program control. *2: If the Auto-tuning is performed, the mode reverts to the PV/SV display.
Operating Instructions Temperature Indicating Controller CF1H Set the temperature of the program in the Sub setting mode, Auxiliary function setting mode 1 and 2. V 1.
Operating Instructions Temperature Indicating Controller CF1H 4.2 Operations The PV display indicates the sensor type and the SV display indicates the rated value selected by Sensor input designation (page 10, 11) for approx. 2 seconds after the power is turned on. See [table 4.2-1]. During this time, all outputs and LED indicators are in their off status. After that, the actual temperature is displayed on the PV display, main setting value on the SV display and starts control.
Operating Instructions Temperature Indicating Controller CF1H (2) Main setting mode In the PV/SV display mode, if the MODE key is pressed, the Main setting mode will be selected. and FAST keys. The setting value can be increased or decreased by pressing the , If the MODE key is pressed, the setting value will be registered and the controller will revert to the PV/SV display.
Operating Instructions Temperature Indicating Controller CF1H SV SV (Auto-tuning Cancel) (Auto-tuning Perform) [Factory adjusted as Auto-tuning Cancel] If the Auto-tuning is released during the process, the PID value reverts to the former value. Main proportional band setting Setting value MODE Cool proportional band setting Setting value MODE Integral time setting Setting value MODE Derivative time setting Setting value MODE V 1.2 • 01/2007 Mode to set the proportional band for Main control.
Operating Instructions Temperature Indicating Controller CF1H Main control proportional cycle setting Setting value MODE Mode to set the proportional cycle of Main control. Setting range: 1 … 120 s [Factory adjusted as 30 s to Relay contact output type, and 3 s to Non-contact voltage output type] This setting item is not available to Current output type. When the ON/OFF action is selected in Control action designation (page 10), this display is not available.
Operating Instructions Temperature Indicating Controller CF1H Alarm 1 (A1) setting Setting value MODE Alarm 2 (A2) setting Setting value MODE Mode to set the action point of the Alarm 1 (A1) output. This item is not displayed if setting the rotary switch to No. 0 or No. 7 (See page 12.) Setting range: See [table 4.2-2]. [Factory adjusted as 0 °C] Mode to set the action point of the Alarm 2 (A2) output.
Operating Instructions Temperature Indicating Controller CF1H Loop break alarm time setting Setting value MODE Loop break alarm span setting Setting value MODE Mode to set the time for Loop break alarm activation assessment. Setting range: 0 … 200 minutes [Factory adjusted as 0 min.] This display is indicated only when the option [2AR or 2AL] is applied. Mode to set the span for Loop Break Alarm activation assessment. Setting range: 0 … 150 °C (Thermocouple, except T and RTD without a decimal point) 0.
Operating Instructions Temperature Indicating Controller CF1H (4) Auxiliary function setting mode 1 In PV/SV display mode, if the MODE key is pressed for approx. 3 seconds while the key is being pressed, Auxiliary function setting mode 1 can be selected. The setting value can be increased or decreased by pressing the , and FAST keys. If the MODE key is pressed, the setting value is registered and the next setting item is selected. PV/SV display mode Actual Main setting Temperature value + MODE for approx.
Operating Instructions Temperature Indicating Controller CF1H As to the Lock mode 3 When using the CF1H as a Fixed value controller. The setting values can temporarily be changed by the selected setting value memory number, however, when the number is changed, the setting values changed by the previous number are canceled and returns to the former values. When using the CF1H as a Program controller.
Operating Instructions Temperature Indicating Controller CF1H Sensor correction function Corrects the input value from the sensor. When a sensor cannot be set at a location where control is desired, the sensor measuring temperature may deviate from the temperature in the controlled location. When controlling with multiple controllers, the accuracy of sensors have influence on the control. Therefore, sometimes the measuring temperature (input value) does not concur with the same setting value.
Operating Instructions Temperature Indicating Controller CF1H Transfer rate selection Selection Mode to select a communication transfer rate to meet the rate of the host computer. [Factory adjusted as 9600 bps] MODE 2400 bps 4800 bps 9600 bps 19200 bps This display is available only when the option [CR2 or CR5] is applied. Communication protocol Selection Mode to select a communication protocol.
Operating Instructions Temperature Indicating Controller CF1H (5) Auxiliary function setting mode 2 In PV/SV display mode, if the MODE key is pressed for approx. 3 seconds while the and keys are being pressed, Auxiliary function setting mode 2 can be selected. and FAST keys. The setting value can be increased or decreased by pressing the , If the MODE key is pressed, the setting value is registered and the next setting item is selected.
Operating Instructions Temperature Indicating Controller CF1H PV filter time constant Setting Setting value MODE Mode to suppress the PV fluctuation caused by such as disturbance. Set the value larger by degrees, and find the setting value at which the value does not fluctuate. If the value is set too large, it affects control result due to the delay of response. Setting range: 0.0 … 10.0 s [Factory adjusted as 0.0 s] Main output high limit setting Mode to set the high limit value of the main output.
Operating Instructions Temperature Indicating Controller CF1H Cooling action mode selection Selection MODE Mode to select the Cooling action, Air cooling, Oil cooling or Water cooling. [Factory adjusted as Air cooling] This display is indicated only when the option [D is applied. 2] Air cooling (linear characteristic) Oil cooling (The 1.
Operating Instructions Temperature Indicating Controller CF1H Alarm 1 (A1) action Energized/Deenergized Mode to select the action Energized or Deenergized for Alarm 1. Selection [Factory adjusted as Energized] MODE This display is not indicated when the rotary switch is set to No. 0 or No. 7 in Alarm 1 action designation (page 12).
Operating Instructions Temperature Indicating Controller CF1H Alarm 1 (A1) action delayed timer setting Setting value MODE Alarm 2 (A2) action delayed timer setting Setting value MODE External setting input high limit setting Setting value MODE External setting input low limit setting Setting value MODE V 1.2 • 01/2007 Mode to set the action delayed timer for Alarm 1.
Operating Instructions Temperature Indicating Controller CF1H Transmission output selection Selection MODE Mode to select the type of Transmission output. [Factory adjusted as PV transmission] This display is indicated only when the option [TA4 or TV1] is applied. Process variable (PV) transmission Main setting value (SV) transmission Manipulating value (MV) transmission Transmission output high limit setting Setting value MODE Transmission output low limit setting Setting value MODE V 1.
Operating Instructions Temperature Indicating Controller CF1H Display selection when control output is off Selection Mode to select the display when the control output is off. [Factory adjusted as indicating OFF on the PV display] MODE OFF is indicated on the PV display. No indication (all unlit). Only PV is indicated. Main setting value rising rate setting Mode to set the rising rate of the main setting value. (Rising value per minute) Setting value Setting the value to 0 or 0.
Operating Instructions Temperature Indicating Controller CF1H Output selection when input burnout Mode to select the control output OFF or not when DC input is over scale or under scale.
Operating Instructions Temperature Indicating Controller CF1H (6) Program mode In PV/SV display mode, if the key is pressed for approximately 3 seconds while the key is being pressed, the Program mode can be selected. The setting value can be increased or decreased by pressing the , and FAST keys. If the MODE key is pressed, the setting value is registered and the next setting item is selected.
Operating Instructions Temperature Indicating Controller CF1H PV/SV display mode Actual temperature Main setting value + for approx. 3 s Program control change Setting value of Control form is changed between Fixed value and Program. fixed value control MODE MODE In Fixed value control, if the MODE key is pressed, the mode will revert to the PV/SV display mode.
Operating Instructions Temperature Indicating Controller CF1H Step 5 Time setting Setting value Mode to set the Time for step 5. [The setting range and the factory adjusted value are the same as Step 1.] MODE Step 6 Time setting Setting value Mode to set the Time for step 6. [The setting range and the factory adjusted value are the same as Step 1.] MODE Step 7 Time setting Setting value Mode to set the Time for step 7. [The setting range and the factory adjusted value are the same as Step 1.
Operating Instructions Temperature Indicating Controller CF1H (8) Control output OFF function A function to turn the control output OFF even if the power to the instrument is supplied. The function is used when required to halt the control action or when the CF1H is not being used in multiple controllers. Control output OFF function can be selected from any mode by pressing the OUT/OFF key for approx. 1 second. The display is the same as when [Display selection when control output is off] is selected.
Operating Instructions Temperature Indicating Controller CF1H (9) Output manipulating value and Step rest time indication mode In the PV/SV display mode, press the MODE key for approx. 3 seconds. The display will be changed to main setting mode in the process, however, keep pressing it until the Output manipulating value is displayed. If the MODE key is pressed again, the mode reverts to the PV/SV display.
Operating Instructions Temperature Indicating Controller CF1H 5. Setting value memory function [Option code: SM7] If the option [SM7] is applied, a maximum of 7 files of data can be memorized, and when selecting a desired file, the desired control can be performed.
Operating Instructions Temperature Indicating Controller CF1H 6 Running After the controller has been mounted to the control panel and wiring is completed, it can be started in the following manner. 6.1 When using the CF1H as a Temperature controller (1) Turn the power supply to the CF1H ON. For approx.
Operating Instructions Temperature Indicating Controller CF1H 6.2 When using the CF1H as a simplified program controller (1) Turn the power supply to the CF1H on. For approx. 2s after the power is turned ON, the type of sensor and the unit designated in Sensor input designation (page 12, 13) are indicated on the PV display, and the rated maximum value is indicated on the SV display. See [table 6.1-1]. During this time, all outputs and LED indicators are in their OFF status.
Operating Instructions Temperature Indicating Controller CF1H 7 Action explanations 7.
Operating Instructions Temperature Indicating Controller CF1H 7.3 ON/OFF action drawings Action Heating (reverse) action Cooling (direct) action Hysteresis Control action Hysteresis ON ON OFF OFF Main setting Current Output Non-contact voltage Relay contact Main setting 4 4 4 4 5 5 5 5 6 6 6 6 + 5 12Vdc + 5 0Vdc + 5 0Vdc + 5 12Vdc 6 6 6 6 + 5 20mAdc + 5 4mAdc + 5 4mAdc + 5 20mAdc 6 6 6 6 Indicator [OUT1] Green Unlit Lit Unlit Lit part: Acts ON or OFF. 7.
Operating Instructions Temperature Indicating Controller CF1H 7.
Operating Instructions Temperature Indicating Controller CF1H Cooling (direct) action in Heating control (Heating P-band) Action Cooling P-band (Heating) Cooling Setting Relay contact 7 7 7 8 8 8 (*1) Cooling output Non-contact voltage + 7 0Vdc + 7 0/12Vdc + 7 12Vdc 8 8 (*1) 8 + 7 4mAdc Current 8 Indicator [OUT2] Yellow Unlit • 01/2007 8 (*2) + 7 20mAdc 8 Lit (*1) Cycle action is performed according to deviation. (*2) Changes continuously according to deviation. V 1.
Operating Instructions Temperature Indicating Controller CF1H Heating (reverse) action in Cooling control (Cooling P-band) Heating P-band Action (Cooling) Heating Setting Relay contact H 4 H 4 H 4 C 5 C 5 C 5 L 6 L 6 (*1) L 6 5 Heating Non-contact output voltage + 0Vdc 6 + 5 0/12Vdc + 5 12Vdc 6 6 (*1) + 5 4mAdc Current 6 + 5 4 to 20mAdc 6 + 5 20mAdc 6 (*2) Indicator [OUT1] Green Lit Unlit (*1) Cycle action is performed according to deviation.
Operating Instructions Temperature Indicating Controller CF1H Cooling (direct) action in Cooling control Cooling P-band Action (Heating P-band) Cooling (Heating) Setting Relay contact 7 7 7 8 8 8 (*1) Cooling output Non-contact voltage Current + 7 12Vdc + 7 12/0Vdc + 7 0Vdc 8 8 (*1) 8 + + 7 7 20mAdc 20 to 4mAdc 8 + 7 4mAdc 8 8 (*2) Indicator [OUT2] Yellow Unlit Lit (*1) Cycle action is performed according to deviation. (*2) Changes continuously according to deviation. V 1.
Operating Instructions Temperature Indicating Controller CF1H When setting Dead band Action Heating action Dead band Proportional band Cooling action Proportional band Control action Setting 4 Relay contact 5 6 4 4 5 7 7 7 8 8 8 5 6 6 (*1) Noncontact Output voltage + 5 12Vdc 6 (*1) + 5 12/0Vdc 6 + 5 0Vdc + 7 0Vdc 6 8 0/12Vdc Current 6 Indicator [OUT1] Green Lit Indicator [OUT2] Yellow Unlit 5 (*1) + 20 to 4 mAdc 6 (*2) + 5 4mAdc 6 • 01/2007 7 + 4mAdc 8 7 + 4 to
Operating Instructions Temperature Indicating Controller CF1H When setting Overlap band with Relay contact output. Heating proportional band Cooling proportional band Overlap band Control action Setting Heating output 4 4 4 5 5 5 6 6 6 (*1) Relay contact output Cooling output 7 7 7 8 8 8 (*1) Indicator [OUT1] Green Lit Indicator [OUT2] Yellow Unlit Unlit Lit (*1) Cycle action is performed according to deviation. V 1.
Operating Instructions Temperature Indicating Controller CF1H 7.
Operating Instructions Temperature Indicating Controller CF1H High/Low limits alarm with standby High/Low limit range alarm with standby Hysteresis Hysteresis Temperature alarm action ON ON OFF OFF Alarm setting Main setting Alarm Main setting setting Alarm setting Alarm setting 9 9 9 9 9 9 10 10 10 10 10 10 Output Indication Lit Lit Unlit Process high alarm Hysteresis Temperature alarm action Unlit Unlit Lit Process low alarm Hysteresis ON ON OFF OFF Alarm setting Alar
Operating Instructions Temperature Indicating Controller CF1H 8. Control actions 8.1 Fuzzy self-tuning Fuzzy self-tuning is a function to perform a fine adjustment of PID values automatically. The stable control can be carried out even if the conditions of the process are changed due to things like change in types and rates of production. (1) When the control is rising, the controller performs the control by the PID values tuned in advance.
Operating Instructions Temperature Indicating Controller CF1H 8.2 Explanations of PID (1) Proportional band (P) Proportional action is the action which the control output varies in proportion to the deviation between the setting value and the processing temperature. If the proportional band is narrowed, even if the output changes by a slight variation of the processing temperature, better control results can be obtained as the offset decreases.
Operating Instructions Temperature Indicating Controller CF1H 8.3 PID auto-tuning of this controller In order to decide each value of P, I, D and ARW automatically, this system gives the fluctuation to the controlling object by force. (1) When the difference between setting value and processing temperature is large when the temperature rises. Fluctuation is given at the temperature 1.5 % of scaling span less than the setting value. 1.
Operating Instructions Temperature Indicating Controller CF1H 9. Other functions (1) Burnout alarm (Upscale) When the thermocouple or RTD is burnt out or the input value exceeds [Rated scale maximum value +1 % of rated scale span], the control output is turned OFF(main output low limit value for the current output type) ]. and the PV display blinks [ With the input RTD Pt100 (°F), if the input value is greater than 999.
Operating Instructions Temperature Indicating Controller CF1H 10. Mounting to control panel 10.1 Site selection Mount the controller in a place with: (1) A minimum of dust and an absence of corrosive gases. (2) No mechanical vibrations or shocks. (3) No exposure to direct sunlight, an ambient temperature of 0 … 50 °C (32 … 122 °F) that does not change suddenly. (4) An ambient non-condensing humidity of 85 %RH or less.
Operating Instructions Temperature Indicating Controller CF1H +0.8 92 0 130 +0.8 92 0 10.3 Panel cutout drawing +0.5 n x 48-3 0 Lateral close mounting n: Number of units mounted +0.5 45 0 [Fig. 10.3-1] 10.4 Current transformer (CT) dimension drawing CTL-6-S (for 20A) CTL-12-S36-10L1 (for 50A) [Fig. 10.4-1] V 1.
Operating Instructions Temperature Indicating Controller CF1H 10.5 Mounting • When using the One-touch type mounting bracket Mounting panel thickness is 1 … 3 mm. Mount one-touch mounting bracket 1 to the body in advance, and then Insert the CF1H 2 from the front of the panel. If Soft front cover is used, the mounting panel thickness will be 1 … 2.5 mm. 1 2 [Fig. 10.5-1] 1 • When using the Screw type mounting bracket [Option code: FS] Mounting panel thickness is 1 … 15 mm.
Operating Instructions Temperature Indicating Controller CF1H 11. Wiring connection Warning Turn the power supply to the instrument off before wiring or checking. Working or touching the terminal with the power switched on may result in Electric Shock, which can cause severe injury or death. Moreover, the instrument must be grounded before the power supply to the instrument is turned on. 11.
Operating Instructions Temperature Indicating Controller CF1H n Recommended terminal Use a solderless terminal with insulation sleeve to fit to M3 screw as shown below. 3.2mm 5.8mm or less 5.8mm or less 3.2mm 11.2 Wiring connection examples Notices • Use a thermocouple and compensating lead wire according to the input specifications of this controller. • Use a 3-wire RTD system according to the input specifications of this controller. • This controller has no built-in power switch or fuse.
Operating Instructions Temperature Indicating Controller CF1H 3-phase * Electromagnetic switch Heater Alarm unit Thermocouple Electric furnace [Fig. 11.2-1] • To prevent the unit from harmful effects of unexpected level noise, it is recommended that a surge absorber be installed between the electromagnetic switch coils. Single-phase Alarm unit 24V SSR CT Heater Thermocouple Electric furnace [Fig. 11.
Operating Instructions Temperature Indicating Controller CF1H • Current transformer (CT1, CT2) input [Option code: W12, W15, W32 or W35] (1) This alarm is not available for detecting current under phase control. (2) Use current transformer (CT) an accessory one, and pass one lead wire of heater circuit into the hole of the CT. (3) When wiring, keep CT wire away from AC source and load wire to avoid the interference from external.
Operating Instructions Temperature Indicating Controller CF1H 12. Specifications 12.1 Standard specifications Mounting method : Flush Setting : Input system using membrane sheet key Display PV display : Red LED display 4 digits, size, 8 (H) x 4 (W) mm SV/MV/TIME display : Green LED display 4 digits, size, 8 (H) x 4 (W) mm Setting value memory number (MEMO) display: Yellow LED display 1 digit, size, 8 (H) x 4 (W) mm Indicating accuracy Thermocouple input : Within ±0.
Operating Instructions Temperature Indicating Controller CF1H Control output Relay contact : 1a1b Control capacity, 250 V AC, 3 A (resistive load) 250 V AC, 1 A (inductive load cosø=0.4) Non-contact voltage : For SSR drive 12+2, 0 V DC maximum 40 mA DC (short circuit protected) Current : 4 … 20 mA DC (Isolated type) Load resistance, maximum 550 Ω Controlling action The fuzzy self-tuning PID, PID, PD or ON/OFF action is selectable by DIP switch.
Operating Instructions Temperature Indicating Controller CF1H Action : ON/OFF action Hysteresis setting range When thermocouple or RTD input, 0.1 … 100.0 °C (°F) When DC input, 1 … 1000 (Decimal point place follows the selection.) : Relay contact 1a Control capacity, 250 V AC, 3 A (resistive load) 250 V AC, 1 A (inductive load cosø =0.
Operating Instructions Temperature Indicating Controller CF1H : Approx. 15 VA : 0 … 50 °C (32 … 122 °F) : 35 … 85 %RH (non-condensing) : Approx.
Operating Instructions Temperature Indicating Controller CF1H 12.2 Optional specifications Alarm 2 output [2AS or 2AL] The alarm action point is set by ±deviation to main setting (except Process value alarm). [When the alarm action is set as energized] When the input exceeds the range, the output turns ON or OFF (in the case of High/Low limit range alarm). [When the alarm action is set as deenergized] The output acts conversely.
Operating Instructions Temperature Indicating Controller CF1H Heating/Cooling control output [DR2, DS2 or DA2] Heating/Cooling control output (D 2) is not available with a combination of Alarm 2 output (A2), Loop break alarm output (LA) or Insulated power output [P24]. The specifications of heating side are the same as the Main output. Cooling side proportional band: Multiplying factor to the heating side proportional band is 0.0 … 10.0. (ON/OFF action when setting the value to 0.0.
Operating Instructions Temperature Indicating Controller CF1H Setting value memory number external selection [SM7] Selects the setting value memory number from 7 files (under mentioned data as one file) by external terminal.
Operating Instructions Temperature Indicating Controller CF1H Dust-proof•Drip-proof [IP4] Dust-proof and Drip-proof specification (IP54) Effective for only panel surface, case part is excluded. To protect the controller from water leak between control panel and controller, take note of the following items. (1) The panel cutout dimension should be proper and have no burrs. (2) The control panel surface to be mounted should be vertical.
Operating Instructions Temperature Indicating Controller CF1H 13. Troubleshooting If any malfunctions occur, refer to the following items after checking the power and the wiring. Warning Turn the power supply to the instrument off before wiring or checking. Working or touching the terminal with the power switched on may result in Electric Shock, which can cause severe injury or death. Moreover, the instrument must be grounded before the power supply to the instrument is turned on.
Operating Instructions Temperature Indicating Controller CF1H Phenomenon If indication of PV display is abnormal or unstable. Phenomenon If setting mode cannot be selected. If settings are impossible. If the value does not change by the , keys. If the setting indication does not change in the rated scale range even if keys the , are pressed, and setting is impossible. If it does not start even if the OUT/OFF key is pressed in the Program mode. V 1.
Operating Instructions Temperature Indicating Controller CF1H Phenomenon If process variable (temperature) does not rise. If it does not control. (Indicates only PV display) If the main output or cooling output has kept its ON status. If the main output or cooling output has kept its OFF status. Presumed cause and the action • Thermocouple or RTD is burnt out.
Operating Instructions Temperature Indicating Controller CF1H 14.
Operating Instructions Temperature Indicating Controller CF1H Character Item Scaling high limit setting Scaling low limit setting Decimal point place selection PV filter time constant Main output high limit setting Main output low limit setting Main ON/OFF action hysteresis Cooling action mode selection Cooling output high limit Cooling output low limit Cooling ON/OFF action hysteresis Alarm 1 action Energized/Deenergized Alarm 2 action Energized/Deenergized Alarm 1 hyst