H07RN-F rubber-sheathed cable:
Use inside dry, humid, and wet rooms,
as well as outdoors, though not directly
in the ground.
UV-resistant to a limited extent.
Minimum bending radius:
4 x outside diameter.
Operating temperature: 60 °C.
A horizontal installation position is preferable in order
to ensure that water drains off.
In accordance with installation regulation
IEC 60364-5-52 (DIN VDE 0100-522.3) cable systems
must be designed in such a way that damage caused
by the ingress of water is avoided.
Cable systems must satisfy the required degree of
protection. If water can accumulate or condensation
of water may occur, provisions for water drainage
must be made. This particularly applies to sealing
points in the area of the strain relief.
If abrasion might occur (in flexible installations),
wear of the pre-assembled cable must be taken into
consideration and must be monitored.
Avoid bending of the cable in the area of the strain
relief.
Control mechanical bending in the area of the strain
relief using suitable measures (e.g. cable clamps).
Direct layout of the system components in the ground
is not possible. According to VDE 0100-520,
connectors must be protected using suitable additional
facilities; they must be accessible for visual inspection,
testing, and maintenance.
The connector system is not designed for continuous
operation under water.
However, unplanned immersion is possible as
foreseen by the specification.