Owner manual
K33
www.hubbell-wiegmann.com
Data Subject To Change Without Notice
FEATURES-SPECIFICATIONS
ENVIRONMENTAL CONTROLS
ETR
& ZR SERIES THERMOSTATS
Industry Standards
UL Recognized Component
cUL Recognized Component
CE Recognized
CSA Rated
ETR202 ETR202F ZR011
Appli cations
ETR202C and ETR202F
• Designed to provide air temperature
control and monitoring in switch
gear enclosures that are set up to
operate with heaters, fans, filter
ventilators, heat exchangers,
and/or signal transmitters.
• When the enclosure reaches the
pre-determined set point, tempera-
ture contacts in the thermostat are
activated and the fan or heater
automatically begins to operate.
• Thermostats prolong the life
expectancy of heaters and fans by
curtailing their operating hours and
also increase the working efficiency
of electrical components by expos-
ing them to fewer contaminants from
the surrounding environment.
ZR011
• The ZR011 houses two separate
thermostats, allowing the independent
control of heating and cooling or
other equipment. Both thermostats
offer wide adjustment ranges and
are color coded for easy function
recognition.
• Switching capacity:
NC: 10A resistive/2A inductive
@250VAC
NO: 5A resistive/2A inductive
@250VACDC30W
CATALOG TEMP. TEMP.
SWITCHING
FOR PRODUCT DIMENSIONS
NUMBER SCALE RANGE TYPE HXWXD
ETR202F Fahrenheit 32-140ºF Normally Closed Heating 2.40x1.30x1.40 (60x33x35)
ETR202 Celsius 0-60ºC Normally Closed Heating 2.40x1.30x1.40 (60x33x35)
ETR201F Fahrenheit 32-140ºF Normally Open Cooling 2.40x1.30x1.40 (60x33x35)
ETR201 Celsius 0-60ºC Normally Open Cooling 2.40x1.30x1.40 (60x33x35)
ZR 011F Fahrenheit 32-140ºF
Normally Closed/
Heating/Cooling 2.60x2.00x1.80 (67x50x46)
Normally Open
ZR 011C Celsius 0-60ºC
Normally Closed/
Heating/Cooling 2.60x2.00x1.80 (67x50x46)
Normally Open
ETR & ZR SERIES THERMOSTATS
Features
• Normally Closed Thermostat— For
the control of fan heaters and heaters
• Normally Open Thermostat—For the
control of cooling units, fans, filter
ventilators or switching, or signal
transmitters in the event of overheating
• Available in Fahrenheit or Celsius scale
• Thermostatic bi-metallic sensor element
• Easily installed by clip mounting on
35mm or 38mm DIN rails
• Housing made from gray flame
retardant UL94-VO plastic
• Connection: 2 pole terminal for max.
14 AWG
• Switching Difference (hysteresis):
12ºF (7ºC)
• Switching Capacity: 15 A (2) AC
120V, 10 A (2) AC 250V, 10A 12V
DC, 5A 24V DC
• Twothermostats in one unit
– one Normally Closed (NC)
and one Normally Open (NO)
– or two Normally Open (NO)
• Eachwithwideadjustable tem-
perature range
• Available with°For°C scale
• DIN rail mountable