SM101PR FB Tri-Pac 8.00 5.38 0.81 6.50 12.50 10.50 16.50 19.50
SM150R F Frame: EHD, FDB, FD, HFD, FDC 8.00 5.38 0.81 6.50 12.50 10.50 16.50 19.50
SM250JR J Frame: JDB, JD, HJD, JDC 8.50 7.50 0.81 10.00 8.00 14.00 17.00
SM400KR K Frame: DK, KDB, KD, HKD 9.06 7.50 0.81 9.62 7.62 13.62 16.62
SM400PR LA Tri-Pac 14.44 9.75 0.81 9.75 7.75 13.75 16.75
SM600R L Frame: LD, HLD, LDC 8.81 7.62 0.81 12.88 15.88
SM800R M Frame: MD, MDS, HMD 10.68 9.75 0.81 10.16 13.16
SM800PR NB Tri-Pac 16.81 9.75 0.81 10.16 13.16
HANDLE USE WITH
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
MECHANISM CIRCUIT BREAKER
FG K
H=60.12 H=72.12 H=72.12 H=84.12 H=90.12
WB WB WB WB WB
EATON CUTLER-HAMMER TYPE SM SAFETY HANDLE MECHANISMS
WIRE BEND SPACE “WB” ABOVE DISCONNECT
TWO DOOR FLOOR-MOUNT
FREESTANDING & M ODU LAR
(PAGES F28-F29 & F45-F46) ( P A GES F32-F49)
COMPLETE OPERATOR AMP FRAME BREAKER BREAKER
MECHANISM RATING TYPE HEIGHT WIDTH
F1S03 225A F Frame: EHD, FDB, FD, HFD 6.00 4.12
F1S03 150A F Frame: HMCP 6.00 4.12
F2S03 250A J Frame: JDB, JD, HJD, JDC 10.00 4.12
F2S03 250A J Frame: HMCP 10.00 4.12
F3S03 400A K Frame: DK, KDB, KD, HKD 10.12 5.50
F3S03 400A K Frame: HMCP 12.45 5.50
F4S04 600A L Frame: LD, HLD, LDC 10.75 8.25
F4S04 600A L Frame: HMCP 12.50 8.25
F7S04 800A M Frame: MD, MDS 16.00 8.25
F5S04 1200A N Frame: ND, HND, NDC 16.00 8.25
F6S04 2500A R Frame: RD, CRD, RDC 16.00 15.50
EATON CUTLER-HAMMER FLEX SHAFT
OPERATOR MECHANISMS
Catalog numbers for complete mechanisms include a flange-mounted handle, flexible shaft and circuit breaker mechanism.
• The last digit of the catalog number denotes the length of shaft (F1S03 = 3-foot shaft). The F, J, K frame Flex Shafts
are available in 3-foot to 10-foot lengths. The L, N, R frame Flex Shafts are available in 4-foot to 6-foot lengths.
Space Occupied by Disconnect
The Flex Shaft
system allows the circuit breaker to be positioned independent from the flange-mounted handle mechanism.
• Refer to National Electrical Code
®
article 430-10(b) for wiring space "WB" required for line side conductors.
• Choose the length of shaft based on placement of the circuit breaker in the enclosure ensuring a 4-inch min. bending
radius for the Flex Shaft.
• Space occupied by circuit breaker is determined by overall height "X", width "Y", wire bend space "WB" and location "G"
as selected from right to left.
For Two Door Floor-Mount NEMA 12 “E” = 7.31 when “H” = 60.12 for up to type SM200
(Pages F28-F29 & F45-F46) “E” = 12.81 when “H” = 72.12 for up to type SM200
“E” = 6.88 when “H” = 60.12 for type SM200 and larger
“E” = 12.38 when “H” = 72.12 for type SM200 and larger
For Heavy Duty Freestanding “E” = 11.31 when “H” = 72.12 for up to type SM200
and Modular Enclosures “E” = 16.81 when “H” = 84.12 for up to type SM200
(Pages F32 - F49) “E” = 19.81 when “H” = 90.12 for up to type SM200
“E” = 10.88 when “H” = 72.12 for type SM200 and larger
“E” = 16.38 when “H” = 84.12 for type SM200 and larger
“E” = 19.38 when “H” = 90.12 for type SM200 and larger
FLOOR-MOUNT FREESTANDING MODULAR SERIES ENCLOSURES
DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION