User guide

F54
www.hubbell-wiegmann.com
Data Subject To Change Without Notice
C361NC 30A No fuse 5.75 7.55 0.56 6.50 12.50 10.50 16.50 19.50
C361SC21 30A 30A-250V H, K, R 8.38 7.55 0.56 6.50 12.50 10.50 16.50 19.50
C361SC61 30A 60A-250V H, K, R 8.38 7.55 0.56 6.50 12.50 10.50 16.50 19.50
C361SC61 30A 30A-600V H, J, K, R 8.38 7.55 0.56 6.50 12.50 10.50 16.50 19.50
C361ND 60A No fuse 5.75 7.55 0.56 6.50 12.50 10.50 16.50 19.50
C361SD22 60A 60A-250V H, K, R 8.38 7.55 0.56 6.50 12.50 10.50 16.50 19.50
C361SD22 60A 30A-600V J 8.38 7.55 0.56 6.50 12.50 10.50 16.50 19.50
C361SD62 60A 60A-600V H, K, R 8.38 7.55 0.56 6.50 12.50 10.50 16.50 19.50
C361SD62 60A 60A-600V J 8.38 7.55 0.56 6.50 12.50 10.50 16.50 19.50
C361NE 100A No fuse 5.56 9.07 0.56 6.06 12.06 10.06 16.06 19.06
C361SE263 100A 100A-250V H, K, R 10.31 9.07 0.56 6.06 12.06 10.06 16.06 19.06
C361SE263 100A 100A-250V H, K, R 10.31 9.07 0.56 6.06 12.06 10.06 16.06 19.06
C361SE263 100A 100A-600V J 10.31 9.07 0.56 6.06 12.06 10.06 16.06 19.06
C361NF 200A No fuse 13.06 10.12 0.56 4.06 10.06 8.06 14.06 17.06
C361SF264 200A 200A-250V H, K, R 13.06 10.12 0.56 4.06 10.06 8.06 14.06 17.06
C361SF264 200A 200A-600V H, K, R 13.06 10.12 0.56 4.06 10.06 8.06 14.06 17.06
TYPE AMP FUSE FUSE
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
NUMBER RATING CLIP CLASS
FGK
H=60.12 H=72.12 H=72.12 H=84.12 H=90.12
WBWB WB WBWB
EATON CUTLER-HAMMER C361 DISCONNECT SWITCHES
WIRE BEND SPACE “WB” ABOVE DISCONNECT
TWO DOOR FLOOR-MOUNT
FREESTANDING & M ODU LAR
(PAGES F28-F29 & F45-F46) (PA GES F32-F49)
C371E 225A F Frame: EHD, FDB, FD, HFD, FDC 6.00 5.62 0.56 7.62 13.62 11.62 17.12 20.12
C371E 150A F Frame: HMCP 6.00 5.62 0.56 7.62 13.62 11.62 17.12 20.12
C371F 225A J Frame: JDB, JD, HJD, JDC 8.94 8.12 0.56 7.50* 13.00 11.44 16.94 20.00
C371F 225A J Frame: HMCP 10.94 8.12 0.56 7.50* 13.00 11.44 16.94 20.00
C371F 400A K Frame: DK, KDB, KD, HKD 9.75 8.12 0.56 7.00* 13.00 11.00 17.00 20.00
C371F 400A K Frame: HMCP 9.75 8.12 0.56 7.00* 13.00 11.00 17.00 20.00
C371G 600A L Frame: LD, HLD, LDC 8.44 12.00 0.56 10.88** 9.38 15.38 18.38
C371G 600A L Frame: HMCP 8.44 12.00 0.56 10.88** 9.38 15.38 18.38
C371K 800A M Frame: MD, MDS 10.25 12.00 0.56 11.81 14.81
C371K 1200A N Frame: ND, HND, NDC 10.25 12.00 0.56 11.81*** 14.81
MECHANISM
AMP
FRAME TYPE
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
RATING
FG K
H=60.12 H=72.12 H=72.12 H=84.12 H=90.12
WB WB WB WB WB
EATON CUTLER-HAMMER C371 CIRCUIT BREAKER OPERATORS
WIRE BEND SPACE “WB” ABOVE DISCONNECT
TWO DOOR FLOOR-MOUNT
FREESTANDING & M ODU LAR
(PAGES F28-F29 & F45-F46) ( P AGES F32-F49)
* Available wire bend space "WB" does not allow cable sizes larger than 4/0 AWG in a 60.12-inch tall enclosure.
** Available wire bend space "WB" does not allow cable sizes larger than 300 MCM.
*** Available wire bend space "WB" does not allow cable sizes larger than 350 MCM in a 90.12-inch tall enclosure when using 4 cable per terminal.
See National Electrical Code
®
, table 373-6(b) for more information. Available wire bend space “WB” is insufficient for use with breakers equipped
with TA1201NB1 terminals.
†For Two Door Floor-Mount NEMA 12 “E” = 7.88 when “H” = 60.12
(Pages F28-F29 & F45-F46) “E” = 13.38 when “H” = 72.12
For Heavy Duty Freestanding “E” = 11.88 when “H” = 72.12
and Modular Enclosures “E” = 17.38 when “H” = 84.12
(Pages F32 - F49) E” = 20.38 when “H” = 90.12
FLOOR-MOUNT FREESTANDING MODULAR SERIES ENCLOSURES
DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION