User guide

Accessories
See pages J1-J22
Blank adapter plates on pages F61
IMPORTANT
Disconnect switch or circuit breakers, operat-
ing handle and operating mechanism are not
furnished with enclosure and must be ordered
separately from the disconnect manufacturer
Oper at or adapter plates are required with the
modular flange disconnect enclosure only and
must be purchased separately. Modular non-
disconnect enclosures do not require a opera-
tor adapter plate. See page F61 to select the
proper operator adapter for the brand and
type of disconnect being used
Disconnect ordering information is located on
page F44
Review space occupied by disconnect draw-
ings on page F43 and disconnect tables on
pages F51-F60 to determine if the disconnect
device you are using will fit the enclosure size
you have selected
A modular enclosure sy stem consists of:
A disconnect (master) enclosure
Any quantity of slave enclosures
Gasket kits to be used between enclosures
End plate
An operator adapter plate or blank adapter
plate
Disconnect device (order from disconnect
manufacturer)
Single and Two Door Enclosures
Left side is open (see drawings on pages F41
and F42)
Master door hinged on left
Master door activates mechanical interlock
which prevents slave enclosures from being
opened first
Doors may be closed in any order
Single and Two Door Slave Enclosures
Both sides are open (see drawings on pages
F41 and F42)
Door cannot be opened until master enclo-
sure is opened or the interlock is defeated
WMOD SERIES ENCLOSURES
NEMA 12 MODULAR FREESTANDING DISCONNECT
FEATURES-SPECIFICATIONS
UL File E64791
CSA File LL66078
www.hubbell-wiegmann.com
Data Subject To Change Without Notice
Applications
Modular single-door and double-door Modular
free-standing enclosures are designed to be
bolted together in a variety of lengths and com-
binations to meet the customer’s specific appli-
cation. Modular disconnects enclosures are
designed to house the following flange-mounted
disconnect switches and circuit breakers:
The Wiegmann universal cutout is used in large
freestand and floorstand enclosures. Operator
Adapter Kits are required in order to install the
various manufacturers’ hardware. Note that 400
A (or greater) disconnect switches and 600 A (or
greater) circuit breakers need to use the “Large”
or “High Amp” cutout, which is provided in the
WA21ABVA kit for Allen-Bradley variable-depth
disconnect switches or the WA21ITE kit for
Siemens ITE Max-Flex
(and select other manu-
facturers) flex-cable devices. The “Large” or
“High Amp” cutout accepts the larger operating
handle whose mounting hole centers are 6.500-
in. apart.
Allen-Bradle y
1494V disconnect switches with flange-mount
variable depth operating mechanisms and
1494V flange-mounted variable depth operat-
ing mechanisms for circuit breakers
140U flexible cable operating mechanisms and
140U molded case circuit breakers
1494C cable-operated disconnect switches
with flange-mount handles
194RC cable-operated flange-mount handles
for use with the NFPA 79 compliant 194R IEC
rotary disconnect switches
Allen-Bradley 1494V-R1, -R2 and -W2 operating
handles and Allen-Bradley 1494F disconnect
devices or 1494D circuit breaker operators will
NOT fit these enclosures.
ABB Controls flange-mounted variable
depth operating mechanisms for disconnect
switches and circuit breakers
Eaton Cutler-Hammer Type C361 discon-
nect switches and operating mechanisms,
and Type C371 circuit breaker operating
mechanisms. Also Type SM safety handle
mechanisms and Flex Shaft
handle oper-
ators for circuit breakers
General Electr ic Type STDA flange han-
dles and variable depth operating mecha-
nisms for disconnect switches and circuit
breakers. Also Spectra Flex
cable opera-
tors for circuit breakers
Siemens ITE Max-Flex
flange-mounted
variable depth operating handles for dis-
connect switches and circuit breakers
Schneider Square D
®
disconnect switches
and circuit breakers used with Class 9422
flange-mounted variable depth operating
mechanisms or cable mechanisms
These enclosures will not receive
Schneider Square D
®
Class 9422 bracket-
mounted disconnect devices or Class
9422TG1 or TG2 devices.
Construction
Bodies and doors fabricated from 10 ga. steel
Removable 10-gauge back panels are includ-
ed and mounted on collar studs
Continuously welded seams ground smooth
Body stiffeners are provided for extra rigidity
Door and side openings are flanged to pro-
vide extra strength and smooth edges
Heavy duty lifting eyes and provisions for fluo-
rescent lighting are provided
Heavy gauge continuous hinges
Grounding provisions provided
3-point padlocking handle on all doors
Doors are supplied with a poured-in-place
polyurethane gasket
Print pocket is provided
Panel supports
Mechanical interlocks come standard on each
enclosure. Parts required to connect interlock sys-
tem between adjacent enclosures are provided
Finish
ANSI 61 gray polyester powder inside and out
over phosphatized surfaces
Back panels are white polyester powder over
phosphatized surfaces
WMOD72X4018U
F40
Industry Standards
UL 508, Type 12
CSA Cer tified, Type 12
NEMA/EEMAC Type 12