ABN12 /1494F & 1494D SERIES ENCLOSURES
DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION
F26
www.hubbell-wiegmann.com
Data Subject To Change Without Notice
••N30 30A No fuse 4.62 6.25 3.25 6.25 8.88
••NF30 30A 30A-250V H, K, R 6.25 6.25 3.25 6.25 8.88
••NF30 30A 60A-250V H, K, R 7.25 6.25 3.25 6.25 8.88
••NF30 30A 30A-600V H, K, R 9.25 6.25 3.25 6.25 8.88
••NF30 30A 60A-600V H, K, R 9.75 6.25 3.25 6.25 8.88
••NF30 30A 30A-600V J 6.50 6.25 3.25 6.25 8.88
••NF30 30A 60A-600V J 6.62 6.25 3.25 6.25 8.88
••N60 60A No fuse 4.62 6.25 2.50 5.25 8.12
••NF60 60A 30A-600V H, K, R 10.38 6.25 2.50 5.25 8.12
••NF60 60A 60A-250V H, K, R 8.38 6.25 2.50 5.25 8.12
••NF60 60A 100A-250V H, K, R 10.88 6.25 2.50 5.25 8.12
••NF60 60A 60A-600V H, K, R 10.88 6.25 2.50 5.25 8.12
••NF60 60A 100A-600V H, K, R 12.88 6.38 2.50 5.25 8.12
••NF60 60A 60A-600V J 7.75 6.25 2.50 5.25 8.12
••NF60 60A 100A-600V J 9.75 6.25 2.50 5.25 8.12
—•N100 100A No fuse 4.62 7.00 3.50 6.25
—•NF100 100A 100A-250V H, K, R 11.38 7.00 3.50 6.25
—•NF100 100A 200A-250V H, K, R 12.25 7.25 3.50 6.25
—•NF100 100A 100A-600V H, K, R 13.38 7.12 3.50 6.25
—•NF100 100A 200A-600V H, K, R 14.75 7.38 3.50 6.25
—•NF100 100A 100A-600V J 10.12 7.00 3.50 6.25
—•NF100 100A 200A-600V J 10.88 7.25 3.50 6.25
——N200 200A* No fuse 7.12 10.00 7.00
——NF200 200A* 200A-250V H, K, R 15.00 10.00 7.00
——NF200 200A* 400A-250V H, K, R 16.56 10.38 7.00
——NF200 200A* 200A-600V H, K, R 17.56 10.00 7.00
——NF200 200A* 400A-600V H, K, R 19.56 10.62 7.00
——NF200 200A* 200A-600V J 13.69 10.00 7.00
——NF200 200A* 400A-600V J 15.00 10.25 7.00
FITS ENCLOSURE DEPTH
TYPE AMP FUSE FUSE
SPACE OCCUPIED
WHEN WHEN WHEN
8.00 10.00 12.00 16.00
NUMBER RATING CLIP CLASS
FG**
E=3.84 E=6.75 E=9.50
(203) (254) (305) (406) WB WB WB
ALLEN-BRADLEY 1494F DISCONNECT SWITCHES
WIRE BEND SPACE “WB” ABOVE DISCONNECT
ABN12 / 1494F (PAGES F20-22)
••
N4/N40 150A 5.81 4.31 3.25 6.12 8.88
EHD, FD, FDB, FDC, HFD, HMCP
•••
N5/N55 225A
General Electric
8.81 4.50 5.34 8.09
TFK, THFK, TFC
•••
N5/N50 250A
C-H
8.81 4.50 5.31 8.06
JD, JDB, JDC, HJD, HMCP
•••
N5/N60 400A
C-H
8.81 5.62 5.44 8.19
KD, KDB, KDC, HKD, HMCP
FITS ENCLOSURE DEPTH
TYPE FRAME BREAKER TYPE
SPACE OCCUPIED
WHEN WHEN WHEN
8.00 10.00 12.00 16.00
NUMBER RATING FRAME SIZE (3POLE)
FG
E=3.84 E=6.75 E=9.50
(203) (254) (305) (406) WB WB WB
ALLEN-BRADLEY 1494D CIRCUIT BREAKER OPERATORS
WIRE BEND SPACE “WB” ABOVE DISCONNECT
ABN12 / 1494D (PAGES F20-22)
* 200 amp switches can be installed only in 12.00-inch (305mm) deep enclosures that have provisions for 200 amp switches.
** The “G” dimension does not include space for auxiliary switches. See Allen-Bradley instructions for additional space required.