User guide
ABN12, SDN12, SDN12PL, N412CD,
N412CSTD, N412CSSSTD, SN4 & SSN4X SERIES ENCLOSURES
DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION
F21
www.hubbell-wiegmann.com
Data Subject To Change Without Notice
SWITCH
AMP FUSE FUSE DISCONNECT DISCONNECT ABN12, SDN12, SDN12PL, N412CD, SN4 & S S N4X
RATING CLIP CLASS HEIGHT X WIDTH Y N412CSTD, N412CSSSTD, SN4 & SSN4X WALL-MOUNTS
TCN-30C 30A No fuse — 5.90 6.20
TCF-30C 30A 30A-250V H, K, R 7.50 6.20
TCF-33C 30A 30A-600V H, K, R 10.15 6.20
TCF-33C 30A 60A-250V H, K, R 8.15 6.20
TCF-33C 30A 30A-600V J 7.50 6.20
TDN-60C 60A No fuse — 5.90 6.20
TDF-60C 60A 30A-600V H, K, R 10.15 6.20
TDF-60C 60A 60A-250V H, K, R 8.15 6.20
TDF-63C 60A 60A-600V H, K, R 10.65 6.20
TDF-63C 60A 60A-600V J 7.50 6.20
TEN-10C 100A No fuse — 5.90 6.20
TEF-10C 100A 100A-250V H, K, R 10.35 6.20
TEF-10C 100A 100A-600V H, K, R 10.35 6.20
TEF-10C 100A 100A-600V J 10.35 6.20
SCHNEIDER SQUARE D
®
CLASS 9422 DISCONNECT SWITCHES USED WITH CABLE MECHANISM 9422-CFT30 & 9422A-1 HANDLE MECHANISM
CABLE TYPE AMP FRAME CIRCUIT BREAKER CIRCUIT BREAKER ABN12, SDN12, SDN12PL, N412CD, S N4 & SSN4X
SWITCH RATING TYPE HEIGHT X WIDTH Y N412CSTD, N412CSSSTD, SN4 & SSN4X WALL- M OUNTS
9422 CGJ30 75A GJL 4.75 3.50
9422 CGJ300 100A GJL 4.75 3.50
9422 CGJ30 100A FAL, FHL 6.00 4.50
9422 CGJ30 250A KAL, KHL 8.00 4.50
9422 CGJ30 400A LAL, LHL, Q4L 11.00 6.00
SCHNEIDER SQUARE D
®
CLASS 9422 CABLE MECHANISM FOR CIRCUIT BREAKERS
Use switches listed above with appropriate cable mechanism and 9422-A1 handle mechanism.
Use cable mechanism with appropriate circuit breaker and 9422-A1 handle mechanism. Cable operators are available in 3-foot, 5-foot, and 10-foot lengths.
Numbers shown (30) are for 3-foot cables.
For enclosures that
accept these devices,
see pages F2-F9.
For enclosures that
accept these devices,
see pages F10-F13.
For enclosures that
accept these devices,
see pages F2-F9.
For enclosures that
accept these devices,
see pages F10-F13.
Mechanisms and circuit breakers listed above will fit any disconnect wall-mounts
on pages F10-F13, or SN4 wall-mounts on pages F2-F9 except as noted.
The last 3 digits of operator mechanism number indicates cable length in inches.
Also 48" cables are available for ED, FD, JD/LD operators, and 60" cables for
MD/ND, PD/RD operators.
For Type 4 applications order handle, cable and circuit breaker separately.
*This operator mechanism can only be installed in catalog number
SDN12603812A (see page F3) which has the appropriate flange cutout.
Space Occupied by Disconnect
• The Siemens ITE Max-Flex
™
cable system allows the disconnect to be posi-
tioned independent from the flange-mounted handle mechanism.
• Refer to National Electrical Code
®
article 430-10(b) for wiring space “WB”
required for line side conductors.
• Refer to Siemens ITE Max-Flex
™
installation instructions for limits on discon-
nect location when 36-inch or 48-inch Max-Flex
™
cables.
• Space occupied by disconnect is determined by overall height “X”, width
“Y”, wire bend space “WB” and location “G” as selected from right to left.
COMPLETE OPERATOR CIRCUIT BREAKER MAXIMUM CIRCUIT BREAKER CIRCUIT BREAKER
CIRCUIT BREAKER TYPE
MECHANISM FRAME AMP RATING HEIGHT X WIDTH Y
FHOE036 ED 125A 6.34 3.00 ED2. ED4. ED6. HED4. HED6
FHOE036 CED 125A 9.58 3.00 CED6
FHOF036 FD 250A 9.50 4.50 FXD6-A, FD6-A, HFD6, FXD6-ETJ, HHFD6, HHFXD6
FHOJ036 CFD 250A 14.25 4.50 CFD6, CFD6-ETI
FHOJ036 JD 400A 11.00 7.50 JXD2, JXD6, JD6, HJD6, HHJD6, HHJXD6, JXD6-ETI
FHOJ036 CJD 400A 17.86 7.50 CJD6, CJD6-ETI
FHOJ036 LD 600A 11.00 7.50 LXD6, LD6, HLD6, HHLD6, HHLDX6, LXD6-ETI
FHOJ036 CLD 600A 17.86 7.50 CLD6, CLD6-ETI
FHOLM036 LMD 800A 16.00 9.00 LMD6, LMXD6, HLMD6, HLMXD6, LMXD6-ETI
FHON048* MD 8 00 A 2 4 .0 0 9. 00 MD2, MXD6, HMD6, HMXD6, CMD6, MXD6-ETI, CMD6-ETI
FHON048* ND 1200A 24.00 9.00 ND6, NXD6, HND6, HNXD6, CND6
SIEMENS ITE CIRCUIT BREAKERS FOR MAX-FLEX
™
OPERATORS
Space Occupied by Disconnect Switch or Circuit Breaker
• Schneider Square D
®
cable mechanisms allows disconnect devices to be
positioned independent from the flange-mounted handle mechanism.
•RefertoNational Electrical Code
®
article 430-10(b) for wiring space "WB"
required for line side conductors.
• Choose cable mechanism length based on placement of disconnect in
enclosure. See Schneider Square D
®
Instruction Bulletin for minimum bend
radius for cable.
• Space occupied by disconnect is determined by overall height “X”, width
“Y”, wire bend space “WB” and location “G” as selected from right to left.