User guide

ABN12, SDN12, SDN12PL, N412CD,
N412CSTD, N412CSSSTD, SN4 & SSN4X SERIES ENCLOSURES
DISCONNECT SPACE OCCUPIED & AVAILABLE WIRING SPACE INFORMATION
F19
www.hubbell-wiegmann.com
Data Subject To Change Without Notice
TDOM1A 30A No fuse 7.75** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1A 30A 30A-250V H, R 7.75** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 30A 30A-600V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 30A 60A-250V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 30A 60A-600V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1A 60A No fuse 7.75** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 60A 60A-250V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 60A 60A-600V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 60A 100A-250V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 60A 100A-600V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1A 100A No fuse 7.75** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 100A 100A-250V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 100A 100A-600V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 100A 200A-250V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM1B 100A 200A-600V H, R 12.38** 5.25 6.18* 7.62 12.12 9.12 12.12
TDOM2 200A No fuse 7.00 9.12 9.50 6.50 9.50
TDOM2 200A 200A-250V H, R 15.38 9.12 9.50 6.50 9.50
TDOM2 200A 200A-600V H, R 15.38 9.12 9.50 6.50 9.50
AMP FUSE FUSE
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
MECHANISM
RATING CLIP CLASS
FG
D=8.00 D=10.00 D=12 OR 16 D=8.00 D=12.00
WB WB WB WB WB
GENERAL ELECTRIC TYPE STDA OPERATORS FOR DISCONNECTS
* Disconnect moved down .88" to fit on panel.
**Dimension applies to 8.00" (203mm) deep enclosures and is .88" less in deeper enclosures.
SDOM1A 150A TEB, TED, THED 7.75** 5.25 6.06* 7.50 12.06 9.06 12.06
SDOM1A 150A TEC 7.75** 5.25 6.06* 7.50 12.06 9.06 12.06
TDOM1B 150A TB1 12.38** 5.25 6.06* 7.50 12.06 9.06 12.06
TDOM1B 150A TEC, TECL 12.38** 5.25 6.06* 7.50 12.06 9.06 12.06
TDOM1C 150A TEL 7.75** 5.25 6.06* 7.50 12.06 9.06 12.06
TDOM1D 150A THLC1 7.75** 5.25 5.12 9.62 6.62 9.62
TDOM3 225A TFJ 10.38 5.75 6.06 10.62 7.62 10.62
TDOM3 225A TFK, THFK, TFL 10.38 5.75 6.06 10.62 7.62 10.62
TDOM4 400A TJJ, TJK4, THJK4, TJL4V 8.25 9.38 5.12 9.69 6.69 9.69
TDOM4 600A TJK6, THJK6, TJ4V, TJL4V 8.25 9.38 5.12 9.69 6.69 9.69
TDOM5 400A TB4, TJH6S 14.25 9.38 5.12 9.69 6.69 9.69
TDOM6 225A TLB2, THLC2 11.75 9.38 9.12 6.12 9.12
TDOM6 400A TLB4, THLC4 11.75 9.38 7.75 4.75 7.75
SDOM1A 150A SPECTRA SE150 7.75** 5.25 6.06* 7.50 12.06 9.06 12.06
SDOM3 250A SPECTR SF250 10.38 5.75 6.06 10.62 7.06 10.06
SDOM4 600A SPECTRA SG600 10.00 7.00 7.93 7.93
AMP
SPACE OCCUPIED
WHEN WHEN WHEN WHEN WHEN
MECHANISM
RATING
FRAME TYPE
FG
D=8.00 D=10.00 D=12 OR 16 D=8.00 D=12.00
WB WB WB WB WB
GENERAL ELECTRIC TYPE STDA OPERATORS FOR CIRCUIT BREAKERS
OPERATORS FOR CIRCUIT BREAKERS
* Disconnect moved down .88" to fit on panel.
**Dimension applies to 8.00" (203mm) deep enclosures and is .88" less in deeper enclosures.
WIRE BEND SPACE “WB” ABOVE DISCONNECT
ABN12, SDN12, SDN12PL, N412CD, SN4 & SSN4X WALL-MOUNTS
N412CSTD, N412CSSSTD & SN4 (PAGES F2-F9) (PAGES F10-F13)
WIRE BEND SPACE “WB” ABOVE DISCONNECT
ABN12, SDN12, SDN12PL, N412CD, SN4 & SSN4X WALL-MOUNTS
N412CSTD, N412CSSSTD & SN4 (PAGES F2-F9) (PAGES F10-F13)