Wide Bank 28 DS3 - Release 2.4 July 2004 5-5
Electrical Installation and Cabling
Cable and Wiring Layout
Cable and Wiring Layout
The figure below shows a typical cable and wiring layout for the Wide Bank 28 DS3. Tie-down loops
are provided on the left and right side of the connector panel for tieing down cables and wires. Because
the low-speed connectors are located in the center of the panel, it is easiest to dress the low-speed cables,
Ethernet, ground, and alarm wiring toward the left side of the chassis (as viewed from rear), with the
remaining cables and power wires dressed toward the right side, as shown.
NOTE: Ferrite Cube RFI Suppressors are Carrier Access part number 010-0051.
Figure 5-2 Cable and Wiring Layout Example
Low-Speed DSX-1 Cables
(shielded)
CLI Management
cable (shielded)
TL1 Cable
DS3 & Clock
Coax Cables
Ethernet Cable
(shielded)
Alarm Wiring
Earth or Building
Ground
Low-Speed
Drain Wires
Connector
Retaining
Screws
Power Cables
NOTE: DSX-1 cables require two ferrite RFI/EMI
suppressors per cable for DS1 circuits, as shown.
E1 circuits require three suppressors per cable.
Connector Latch
Tie Down
Ferrite
Cubes