Physical Installation
Mounting the Wide Bank 28 DS3
Rack Mounting - FFO-Equipped Units
Fan Faceplate Option ... 4-9
Rack Mounting (High-Density) ... 4-10
High-density mounting of the Wide Bank requires additional cooling
capability provided by the Fan Faceplate Option (FFO). Any Wide Banks
mounted with less than one rack unit of space between them must have
the FFO option installed.
With FFO the Wide Bank meets NEBS thermal performance criteria for
installation of up to 40 units per rack with no space between units (see
Figure 4-5 and Figure 4-7).
Fan Faceplate Option
The Fan Faceplate Option provides additional cooling capacity to
allow the Wide Banks to be mounted with no space between them.
When fan faceplates are installed, the fan power connectors on the
faceplates mate with power connectors on the Controller cards (see
Figure 4-6). When installing a faceplate, use care to ensure correct
alignment of the power connectors before tightening the fastening
screws at each end of the faceplate. Also, the fastening screws must
be tightened with an adequate tool for compliance with UL 1950. Do
not overtighten.
The fans start operating 30 seconds after the FFO is installed.
Figure 4-5 Standard Rack Fully Loaded with FFO-Equipped Units
NOTE: Pre-FFO Wide Banks can be converted to FFO units. The conversion requires
new Controller cards that can accommodate a Fan Faceplate and loaded with software
release 2.0 or higher.