User manual

Wide Bank 28 DS3 - Release 2.4 July 2004 4-7
Physical Installation
Mounting the Wide Bank 28 DS3
Vertical Mounting in a Standard EIA or WECO Rack
This mounting configuration requires an ambient air temperature below 77
º
F (25
º
C),
without supplemental cooling. In spaces where ambient temperature can rise above
77
º
F, install a fan tray (600 CFM or more) below the rows of Wide Banks. The fan tray
must direct the air up through the units.
The Wide Banks can be vertically mounted in either a standard EIA/WECO 19-inch
rack or a standard EIA/WECO 23-inch rack using the mounting brackets shipped with
the unit, and optional Carrier Access Vertical Mount Crossbars (PN 710-0003 for 19-
inch racks and PN 710-0004 for 23-inch racks). See Figure 4-4 for an illustration of
mounting in both sizes of racks.
Figure 4-4 Vertical Mounting in 19-inch and 23-inch Racks
FUSE PANEL
FUSE PANEL
FAN TRAY
FUSE PANEL
FUSE PANEL
FAN TRAY