User manual

Physical Installation
Mounting the Wide Bank 28 DS3
4-6 July 2004 Wide Bank 28 DS3 - Release 2.4
Rack Mounting - Non-FFO Equipped Units
Horizontal Mounting in a Standard EIA or WECO Rack ... 4-6
Vertical Mounting in a Standard EIA or WECO Rack ... 4-7
NOTE: When mounting Non-FFO Wide Banks horizontally in the same rack,
follow the mounting instructions below to meet the NEBS Operating Temperature
Criteria and to allow sufficient cooling to prevent thermal shutdown under
maximum load conditions.
Horizontal Mounting in a Standard EIA or WECO Rack
Mount Wide Banks, as shown in Figure 4-3, in groups of up to four units, with the units in each
group separated by one rack unit (1 3/4 inches). Separate the four-unit groups with four rack
units (7 inches of open space. The Wide Banks can be horizontally mounted in either a standard
EIA 19-inch rack or a standard EIA/WECO 23-inch rack using the mounting brackets shipped
with the unit.
Figure 4-3 Horizontal Mounting in a Standard Rack
FUSE PANEL
FUSE PANEL
At least 4
rack units
(7 inches)
of empty
space
Up to 4
Wide
Banks
At least 1
rack unit
(1.75 inches)
between
units
4 RU
4 RU
4 RU