User manual

Technical Specifications
Specifications
3-6 July 2004 Wide Bank 28 DS3 - Release 2.4
Power
Two three-terminal (–48, Return, Ground) removable wiring connectors provided for A and
B power feeds
Input Voltage: –42 to –58 VDC
Input current, worst case (–42 VDC):
Fully-redundant with FFO: 0.9 Amp (A and B inputs combined)
Single Controller with redundant DS1s and FFO: 0.6 Amp
Inrush current: 15 Amps for 100 microseconds
Power dissipation:
Fully redundant with FFO: 36 Watts (123 BTU/hour)
Fully redundant, non-FFO: 32 Watts (109 BTU/hour)
Single Controller with redundant DS1s, non-FFO: 22 Watts (75 BTU/hour)
Redundant power sharing at the +5V logic level
Internal solid-state (fuseless) over-voltage and over-current protection
External inline power fuse recommended: One 3 Amp slow-blow for each power feed
Optional Power Converter/Battery Charger (Carrier Access P/N 730-0116):
115 VAC to –48 VDC
Optional Battery Unit (Carrier Access P/N 730-0114):
Provides 6 to 8 hours backup power
Two backup systems provide 8 to 12 hours backup power
Environmental
Altitude: 0 to 15,000 ft. (0 to 4,572 m)
Humidity: 0 to 98% (noncondensing)
External Operational Temperature Range (ambient air):
Meets NEBS operating temperature criteria of 23
º
F to 104
º
F (–5
º
C to 40
º
C) for an indefinite
period, and up to 131
º
F (55
º
C) for 96 hours (4 days) continuous for a maximum of 15 days
per year
Thermal Protection: Automatic power supply shut-down at 176
º F
(80
º
C
)
ambient
Physical Dimensions
Height: 1.75 inches (4.45 cm) - mounting brackets fit 1.75-inch and 2-inch hole spacing
Depth: 10 inches (25.4 cm) - 10.9 inches (27.6 cm) with fan faceplate installed
Width: 17 inches (43.2 cm) - mounting brackets fit 19-inch and 23-inch racks