Installation Guide

STEP 2 – Setup
LVD Warning Beeper
DOWN: Beeper ON
UP: Beeper OFF
Power Mode
DOWN: Always On
UP: Standby
LVD
DOWN: 11.5 V
UP: 10.5 V
Comm. Select
DOWN: Meterbus
UP: Modbus
UP
DOWN
Figure 2 DIP Switch Functions
DIP Switch 1 - Power Mode
Select the desired power mode. In the Always ON mode, the inverter provides
continuous AC output. Standby mode is an energy saving mode. When an AC
load greater than 8W is detected, the AC Output is automatically turned on.
When the total load falls below 8 Watts , the AC Output is automatically turned
off to conserve energy. Loads are detected in one (1) second or less.
Down Position: Always ON (factory default)
Up Position: Standby Mode
DIP Switch 2 – Low Voltage Disconnect
Select the Low Voltage Disconnect (LVD) and Reconnect (LVR) setpoints.
Down Position: LVD = 11.5V, LVR = 12.6V (factory default)
Up Position: LVD = 10.5V, LVR = 11.6V
DIP Switch 3 – LVD Warning Beeper
Enable or disable the LVD audible Warning Beeper.
Down Position: Beeper Warning ON
Up Position: Beeper Warning OFF
DIP Switch 4 – Communications Select
Specify the desired RJ-11 communication protocol. Select Meterbus for
Morningstar remote meters and other Morningstar products. Select Modbus
protocol for PC communications. An adapter is required (not included)
Down Position: Morningstar Meterbus (factory default)
Up Position: Modbus Protocol
6