Installation Guide

5 Connection
SMA Solar Technology America LLC
Installation manualRoofCommKit-P2-US-IA-xx-1114
5 Connection
5.1 Connecting the Gateway
Requirements:
If several Gateways are present in the system, these have to be connected to each other prior
connection to the module in the inverter.
A maximum of threeGateways can be connected to one module in the inverter.
A terminator must be plugged into the last gateway in the row.
Cabling plan of the Gateways:
B A
_
+B A
_
+ B A
_
+ B A
_
+B A
_
+ B A
_
+
B A
_
+B A
_
+
+ B A S
Figure 4 : Cabling plan of the Gateways with module in the inverter
Cable requirements for the communication cable between Gateway and inverter:
Number of conductors: 4
Conductor cross-section: at least 0.22mm² (24AWG)
Maximum external diameter: 8mm (0.31in)
Maximum cable length: 305m (1000ft)
The conductors should be twisted pairs if the total length of the communication cable exceeds
61m (200ft).
The conductors should be shielded if the cable is laid in a nonmetallic cable raceway.
UV-resistant for outdoor use
The conductors lengths in the inverter must be as short as possible. This prevents contact with
live conductors.
If the conductor is to be installed without conduit, the conductor has to be suited for outdoor
use.
If the conductor is to be installed in a conduit together with live conductors, the conductor has
to be insulated for 600V.
ENGLISH