Manual

6 Troubleshooting
SMA Solar Technology AG
User ManualSBxx-US-1XP-40-BA-en-1368
12. Recommission the inverter (see inverter installation manual).
13. If the inverter still displays an insulation error, contact the Service (see Section9, page72).
The PV modules might not be suitable for the inverter in the present quantity.
6.4 Resetting the Operation Inhibition after Detection of an
Arc Fault
If the red LED is glowing and the event number 4301 is shown on the display and/or in the event
list on the user interface of the inverter, the inverter has detected an electric arc and interrupts feed-
in operation.
There are two options for resetting the operation inhibition:
Reset the operation inhibition by tapping twice on the enclosure lid of the Connection Unit.
Reset the operation inhibition by parameter setting.
Reset the operation inhibition by tapping twice on the enclosure lid of the
Connection Unit
1.
DANGER
Danger to life due to electric shock
Disconnect the inverter from any voltage sources (see the inverter installation manual).
2. Ensure that the PV modules, the connected DC cables and the terminal block for the DC
connection are not defective.
Repair or replace defective PV modules, DC cables or terminal block for the DC connection.
3. Recommission the inverter (see inverter installation manual).
4. If the event with the event number 4301 appears in the display, immediately tap on the
enclosure lid twice in quick succession. Here, the operation inhibition can only be reset if the
event is showing in the display when you begin tapping.
This effects resetting of the operation inhibition and the inverter will start feeding in again. At
the same time, the blue LED can flash rapidly, indicating that there is an active WPS function.
The WPS function deactivates automatically after a short period.
Reset the operation inhibition by parameter setting
1.
DANGER
Danger to life due to electric shock
Disconnect the inverter from any voltage sources (see the inverter installation manual).
2. Ensure that the PV modules, the connected DC cables and the terminal block for the DC
connection are not defective.
Repair or replace defective PV modules, DC cables or terminal block for the DC connection.
3. Recommission the inverter (see inverter installation manual).
4. Activate the user interface (see Section4.2, page22).