Installation Guide
10.0 Appendix
85TriStar MPPT-600V Operator’s Manual
84
Technical Specications
84
86
88
90
92
94
96
98
100
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
Efficiency (%)
Efficiency (%)
Efficiency (%)
Power Output (W)
Power Output (W)
Power Output (W)
300
Vmp,
52
Vba
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2100
2200
2300
2400
2500
2600
2700
2800
2900
3000
400 Vmp, 52 Vba
-
80
82
84
86
88
90
92
94
96
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
200 Vmp,
52 Vba
Figure 9-3. Efciency Curves
Efciency
*Ampacity for not more than three current-car-
rying conductors in a raceway, cable, or earth
(buried).
1-Way Wire Distance (meters), 48 Volt System
Wire
Size
(mm
2
)
60
Amps
55
Amps
50
Amps
45
Amps
40
Amps
35
Amps
30
Amps
25
Amps
20
Amps
15
Amps
70
27.3 29.8 32.8 36.4 41.0 46.8 54.6 65.6 82.0 109.3
50
21.7 23.6 26.0 28.9 32.5 37.1 43.3 52.0 65.0 86.6
35
13.6 14.9 16.3 18.2 20.4 23.3 27.2 32.7 40.8 54.5
25
8.6 9.4 10.3 11.4 12.9 14.7 17.2 20.6 25.7 34.3
16
5.4 5.9 6.5 7.2 8.1 9.2 10.8 12.9 16.1 21.5
10
3.4 3.7 4.1 4.5 5.1 5.8 6.8 8.1 10.2 13.6
6
2.1 2.3 2.6 2.8 3.2 3.7 4.3 5.1 6.4 8.5
4
1.3 1.5 1.6 1.8 2.0 2.3 2.7 3.2 4.0 5.3
2.5
0.8 0.9 1.0 1.1 1.3 1.4 1.7 2.0 2.5 3.4
Table 9.2 Maximum 1-way wire distance for 48V systems, stranded copper
2% Voltage Drop Charts for 75°C Stranded Copper Wire
1-Way Wire Distance (feet), 48 Volt System
60
Amps
55
Amps
50
Amps
45
Amps
40
Amps
35
Amps
30
Amps
25
Amps
20
Amps
15
Amps
00
89.6 97.8 107.5 119.5 134.4 153.6 179.2 215.1 268.9 358.5
0
71.0 77.5 85.2 94.7 106.6 121.8 142.1 170.5 213.1 284.2
2
44.7 48.7 53.6 59.6 67.0 76.6 89.3 107.2 134.0 178.7
4
28.1 30.7 33.8 37.5 42.2 48.2 56.3 67.5 84.4 112.6
6
17.7 19.3 21.2 23.5 26.5 30.3 35.3 42.4 53.0 70.6
8
11.1 12.2 13.4 14.9 16.7 19.1 22.3 26.7 33.4 44.6
10
7.0 7.6 8.4 9.3 10.5 12.0 14.0 16.8 21.0 28.0
12
4.4 4.8 5.3 5.8 6.6 7.5 8.8 10.5 13.1 17.5
14
2.8 3.0 3.3 3.7 4.1 4.7 5.5 6.6 8.3 11.0
Table 9.1 Maximum 1-way wire distance for 48V systems, stranded copper
Notes:
• The specied wire length is for a pair of conductors from the solar or battery source to the
controller (1-way distance)
• Shaded cells in the table indicate that the current exceeds the ampacity of the wire for a
given ambient temperature as dened in the following table:
Wire Ampacity* Key
Exceeds wire ampacity at 60°C ambient temperature
Exceeds wire ampacity at 50°C ambient temperature
Exceeds wire ampacity at 40°C ambient temperature
Exceeds wire ampacity at 30°C ambient temperature