Installation Guide

79 TriStar MPPT-600V-TR Operator's Manual
78
Warranty and Policies
10.0 Appen-
dix
10.0 Appen-
dix
WARRANTY CLAIM PROCEDURE
1. Before proceeding, please refer to product manual, including Troubleshooting section.
2. Contacting your authorized Morningstar distributor or dealer from whom you purchased the unit is
the first step in the warranty process. Local dealers can often address warranty issues quickly.
3. If supplier is unable to address the issue, please contact Morningstar by e-mail (support@morning-
starcorp.com) with:
(A) purchase location -- business or company name
(B) full model and serial numbers (SN is 8-digits on unit
bar label)
(C) failure behavior, including LED indications
(D) array configuration, panel Pmax, Voc, Vmp, Isc, and
nominal battery voltage; these specifications are
needed to receive assistance.
(E) multi-meter available (for field troubleshooting)
4. After warranty replacement has been approved and new unit(s) received, please return failed
unit(s) using pre-paid shipping label, and follow any product specific instructions if requested by
Morningstar Warranty Dept.
5. If instructed by Morningstar, after warranty replacement shipment has been received, return of
failed unit(s) is
required before further warranty replacements can be
considered for the original or future cases.
NOTE: Please do not return units without an RMA or case number. Doing so will increase the
time required to resolve your claim.
9.0 Technical Specications
REFER TO THE INCLUDED GFPD-600V OPERATOR'S MANUAL FOR THAT PRODUCT'S
SPECIFICATIONS
Electrical
TS-MPPT-60-600V-48-DB-
TR
TS-MPPT-60-600V-48-DB-
TR-GFPD
Nominal System Voltage 48 volts 48 volts
Maximum Battery Current 60 amps 60 amps
(63A breaker included)
Maximum Solar Input Voltage 600 volts dc 600 volts dc
Battery Operating Voltage Range 16 - 72 volts dc 16 - 72 volts dc
Maximum Operating Input Current
15 amps 15 amps
Nominal Maximum Input Power* 3200 watts 3200 watts
Voltage Accuracy 0.1 % ± 100 mV 0.1 % ± 100 mV
Self consumption (tare loss) 2-3.5 watts 2-3.5 watts
Transient Surge Protection 4500 watts / port 4500 watts / port
*These power levels refer to the maximum wattage the TS-MPPT-60-600V-48 can process. Higher power arrays
can be used without damaging the controller.
Battery Charging
Charging algorithm 4 - stage
Charging stages Bulk, Absorption, Float, Equalize
Temperature compensation coefcient -5 mV / °C / cell (25 °C ref.)
Temperature compensation range (RTS connected) -30 °C to +80 °C
Temperature compensated set-points: Absorption, Float, Equalize, HVD
Charging Set-points (48 volt systems):
Settings
Switches
Battery
Type
Absorp.
Stage
Float
Stage
Equalize
Stage
Absorp.
Time
Equalize
Time
Equalize
Timeout
Equalize
Interval
sw: 4-5-6 Volts Volts Volts Minutes Minutes Minutes Days
off-off-off 1 - Sealed* 56.00 54.80 150
off-off-on 2 - Sealed* 56.60 54.80 57.60 150 60 120 28
off-on-off 3 - Sealed* 57.20 54.80 58.40 150 60 120 28
off-on-on 4 - AGM/Flooded 57.60 54.80 60.40 180 120 180 28
on-off-off 5 - Flooded 58.40 54.00 61.20 180 120 180 28
on-off-on 6 - Flooded 58.80 54.00 61.60 180 180 240 28
on-on-off 7 - L-16 61.60 53.60 64.00 180 180 240 14
on-on-on 8 - Custom Custom Custom Custom Custom Custom Custom Custom
* “Sealed” battery type includes gel and AGM batteries
See section 4.2 for more information