Installation Guide

68
Testing and Troubleshooting
Problem:
Cannot connect to the controller via Ethernet
Solution:
See the Morningstar Product Connectivity Manual, available on our website:
http://www.morningstarcorp.com/wp-content/uploads/2014/02/MS-Comm-Document-2010.pdf
GFPD-600V
Test Button Uses:
The test button can be used for three purposes:
1. With the GFPD-600V in normal mode, pressing the test button conducts a system test that opens
the breaker, shows a red solid LED, and sounds the buzzer;
2. When a ground-fault error has occurred, pressing the test button resets the GFPD-600V to the
normal condition;
3. When a wiring error / open breaker alarm has occurred, pressing the test button resets the
GFPD-600V to the normal condition.
Faults and Corrections:
When a ground-fault error has occurred, push the test button and then close the breaker to
resume normal operation. Have a qualified technician investigate the ground-fault cause.
♦ When a wiring error / open breaker alarm has occurred, correct wiring error and/or close breaker.
Push the test button to resume normal operation.
♦When the low battery voltage threshold of nine volts is reached, the buzzer will sound. To
resume normal operation, re-charge or replace the battery powering the GFPD-600V.
♦Push the test button to perform a system test. Close the breaker to resume normal operation.
♦A critical fault indicates a hardware malfunction. Please contact Morningstar for instructions.
♦ If previous trouble-shooting does not correct the problem, re-start the unit by removing in-line
source fuse, and re-installing.
69TriStar MPPT 600V-TR Operators Manual
Your TS-MPPT-600V-TR will provide years of reliable and trouble-free service. The unit contains
no electromechanical parts such as relays or cooling fans that can wear out and fail. Additionally,
there are no user-serviceable parts inside the controller.
7.1 Important Safety Instructions
SAVE THESE INSTRUCTIONS.
This manual contains important safety, installation and operating instructions for the
TS-MPPT-600V-TR solar controller. The following symbols are used throughout this manual to
indicate potentially dangerous conditions or mark important safety instructions:
WARNING:
Indicates a potentially dangerous condition. Use extreme caution
when performing this task.
!
CAUTION:
Indicates a critical procedure for safe and proper operation of the
controller.
NOTE:
Indicates a procedure or function that is important for the safe and
proper operation of the controller.
AVERTISSEMENT :
Indique une condition potentiellement dangereuse. Faites preuve
d’une prudence extrême lors de la réalisation de cette tâche.
!
PRUDENCE :
Indique une procédure critique pour l’utilisation sûre et correcte du
contrôleur.
REMARQUE :
Indique une procédure ou fonction importante pour l’utilisation sûre et
correcte du contrôleur.
Safety Information
Read all of the instructions and cautions in the manual before beginning installation.
There are no user serviceable parts inside the TS-MPPT-600V-TR. Do not disassemble
or attempt to repair the controller.
WARNING: RISK OF ELECTRICAL SHOCK.
NO POWER OR ACCESSORY TERMINALS ARE ELECTRICALLY ISOLATED FROM
DC INPUT, AND MAY BE ENERGIZED WITH HAZARDOUS SOLAR VOLTAGE. UNDER CER-
TAIN FAULT CONDITIONS, BATTERY COULD BECOME OVER-CHARGED. TEST BETWEEN
ALL TERMINALS AND GROUND BEFORE TOUCHING.
Maintenance and Service7.0