Product Specifications

Power Optimizer for North America
P860
PV SYSTEM DESIGN USING A SOLAREDGE INVERTER
(5)
THREE PHASE 208V
(6)
THREE PHASE 480V
MinimumStringLength
PowerOptimizers
8 13
PVModules 16 26
MaximumStringLength
PowerOptimizers
30 30
PVModules 60 60
MaximumPowerperString
7200
(7)
15300
(8)
W
ParallelStringsofDifferentLengthsorOrientations
Yes
INPUT
RatedInputDCPower
(1)
860
W
Connecontype Dualinputforindependentlyconnectedmodules
AbsoluteMaximumInputVoltage
(Vocatlowesttemperature)
60 Vdc
MPPTOperangRange 12.5-60 Vdc
MaximumShortCircuitCurrent(Isc) 22 Adc
MaximumShortCircuitCurrentperinput(Isc)
11
Adc
MaximumEciency 99.5 %
WeightedEciency 98.6 %
OvervoltageCategory II

MaximumOutputCurrent 18 Adc
MaximumOutputVoltage 85 Vdc

SafetyOutputVoltageperPowerOpmizer 1±0.1 Vdc

PhotovoltaicRapidShutdownSystem CompliantwithNEC2014,2017
(2)
EMC FCCPart15ClassB,IEC61000-6-2,IEC61000-6-3
Safety IEC62109-1(classIIsafety),UL1741
Material UL-94(5-VA),UVResistant
RoHS Yes

CompableSolarEdgeInverters Threephaseinverters
MaximumAllowedSystemVoltage 1000 Vdc
Dimensions(WxLxH)
128x162x59/5x5.6x2.32
mm/in
Weight(includingcables) 1064/2.34 gr/lb
InputConnector MC4DualInput
(3)
OutputWireType/Connector DoubleInsulated;MC4
OutputWireLength
6.9/2.1 ft / m
OperangTemperatureRange
(4)
-40-+85/-40-+185 ˚C/˚F
ProteconRang IP68/NEMA6P
RelaveHumidity 0-100 %
(6)
P860designwiththreephase208Vinvertersislimited.UsetheSolarEdgeDesignerforverification.
(1)
RatedSTCpowerofthemodule.Moduleofupto+5%powertoleranceallowed.
(2)
NEC2017requiresmaxcombinedinputvoltagebenotmorethan80V.
(3)
InacaseofoddnumberofPVmodulesinonestring,itisallowedtoinstalloneP860 poweroptimizerconnectedtoonePVmodule.WhenconnectingasinglemoduletoP860,
sealtheunusedinputconnectorswiththesuppliedpairofseals.
(4)
Forambienttemperatureabove+70˚C/+158˚Fpowerde-ratingisapplied.RefertoPowerOptimizersTemperatureDe-RatingApplicationNoteformoredetails.
© SolarEdge Technologies, Inc. All rights reserved. SOLAREDGE, the SolarEdge logo, OPTIMIZED BY SOLAREDGE
are trademarks or registered trademarks of SolarEdge Technologies, Inc. All other trademarks mentioned herein
are trademarks of their respective owners. Date: 10/2018/V01/ENG NA. Subject to change without notice.
(7)
ForSE14.4KUS/SE43.2KUS:Itisallowedtoinstallupto6,500Wperstringwhen3stringsareconnectedtotheinverter(3stringsperunitforSE43.2KUS)andwhenthemaximumpowerdifferencebetweenthe
stringsisupto1,000W.
(8)
ForSE30KUS/SE33.3KUS/SE66.6KUS/SE100KUS:Itisallowedtoinstallupto15,000Wperstringwhen3stringsareconnectedtotheinverter(3stringsperunitforSE66.6KUS/SE100KUS)andwhenthemaximum
powerdifferencebetweenthestringsisupto2,000W.
(5)
It is not allowed to mix P860 with P730/P800p/P850 in one string or to mix with P300/P320/P400/P405 in one string.


860
