Networking and Communication
Serial Port Settings
Adjust the serial port settings as follows:
9600 BAUD
8 data bits
1 or 2 stop bits
no parity
The serial RS-232 connection provides a direct connection between a TriStar MPPT 150V and a
PC (or other serial device). Firmware updates can only be programmed through the RS-232
connection. The serial connection is not typically used for multi-controller networking. However,
networking is possible using a USB hub and USB-Serial cables. For more information, refer to
the “Morningstar Communications Document” on our website at:
www.morningstarcorp.com
5.4 EIA-485 (formerly RS-485)
NOTE:
The EIA-485 connection is only available on the TS-MPPT-60/M model.
NOTE:
The RS-232 and EIA-485 ports share hardware. Both ports cannot be used simultaneously.
EIA-485 is a networking standard for serial communication between multiple devices on a bus.
The TriStar MPPT 150V communicates over an EIA-485 network via the open standard MOD-
BUS
TM
protocol. Use EIA-485 networking to:
connect multiple TriStar MPPT 150V controllers on a network to log and view real-time
data using MSView
TM
PC software
program each controller on the network with custom charge settings using MSView
TM
PC
software
connect the TriStar MPPT 150V to other Morningstar controllers with the RSC-1 Serial to
EIA-485 Adapter (sold separately)
bridge an Ethernet connection through a TriStar MPPT 150V to an EIA-485 network
The EIA-485 port has four (4) connections: Power, Data A, Data B, and Ground. Data A & B are
differentially driven data lines that carry the network data. Power and Ground connections pro-
vide power to the network. The TriStar MPPT 150V does not supply power to the EIA-485 net-
work, therefore an external power source is required. The source voltage must be between 8-16
Vdc. For 12 Volt systems, the network can be powered directly from the system battery. Use a
DC-DC converter for 24, 36, and 48 Volt systems.
!
CAUTION: Equipment Damage
Tapping power off of individual batteries in a series string of batteries can cause a voltage imbalance.
Damage to the batteries may result. Always use a DC-DC converter to power the EIA-485 network if the
nominal system voltage is greater than 12 volts.
!
PRUDENCE : Endommagement de l’équipement
L’arrêt progressif de batteries individuelles dans une série de batteries peut provoquer un déséquilibre
de tension. Les batteries peuvent être endommagées. Utilisez toujours un convertisseur CC-CC pour
convertir l’alimentation au réseau EIA-485 si la tension nominale du système est supérieure à 12 V.
For more information on EIA-485 networking, refer to the “Morningstar Communications Docu-
ment” on our website at:
HTTP://www.morningstarcorp.com/