Installation Guide

MORNINGSTAR CORPORATION 51
4.0
4.0 OPERATION
50
AVERTISSEMENT: Risque de décharge
électrique
Un moyen de déconnexion de tous les poteaux
d'alimentation doit être fourni. Ceux-ci se déconnecte
doit être intégrée dans le câblage xe. Ouvrir que toutes
les source d'énergie se déconnecte avant de retirer le
couvercle de la contrôleur, ou accès au câblage.
The following inspections and maintenance tasks are
recommended at least two times per year for best controller
performance.
Tighten all terminals. Inspect for loose, broken, or
corroded connections.
Verify that all wire clamps and tie-downs are secure.
Check that the controller is mounted in a clean,
protected environment; free of dirt, insects, nests,
and corrosion.
If applicable, check enclosure ventilation and air ow
holes for obstructions.
Verify LED indication is consistent with the present
system conditions.
Verify that the Remote Temperature Sensor (if
used) is securely attached to the RTS terminals.
4.7 Programming Custom Set-points
CAUTION: This feature should only be used by advanced
users who have very specic charging and/or load control
requirements that are not met using the factory default charge
and load control settings. The factory default settings will be
sufcient for the vast majority of users.
Custom charging and load set-points can be programmed into
SS-MPPT non-volatile memory using a PC with Morningstar MSView
software installed, and a Meterbus to Serial Adapter (Model: MSC)
or a USB Meterbus Converter (Model: UMC-1). Refer to the MSView
help les for detailed instructions. MSView PC software is available at
no charge on our website at:
www.morningstarcorp.com
The SS-MPPT Set-up Wizard will guide you through the
set-point conguration process. Refer to MSView Help les for more
information.
To use custom set-points, the Settings Switches must be adjusted as
follows:
SWITCH #1 ON (↑) TO USE CUSTOM CHARGING SET-POINTS.
USE THE BATTERY SELECT JUMPER TO SELECT BETWEEN
TWO SETS OF CUSTOM CHARGING SET-POINTS.
SWITCH #2 ON (↑) TO USE CUSTOM LOAD CONTROL
SET-POINTS.
NOTE: Use the custom settings wizard to congure and
program the controller for Lighting load control. This
functionality can only be enabled through custom settings.
NOTE: Programming custom set-points will overwrite the
default Gel and AGM battery type values programmed into
custom memory at the factory. Document the new
custom values in this manual for future reference.
!