Installation Manual
Power Optimizer Troubleshooting
Iftheinverterstatusscreenindicatesthatnotallpoweroptimizersarepairedornotall
arereporting(P_OKxxx/yyy,andx<y),thoseoptimizerscanbeidentifiedthroughthe
LCD.Refertohttps://www.solaredge.us/sites/default/files/non_reporting_power_
optimizers.pdf
Problem
Possible cause and
troubleshooting
Pairing failed
Power optimizers are shaded.
If you connected the inverter to the monitoring
platform, retry pairing remotely (during
sunlight). Make sure to leave the inverter
ON/OFF switch ON and that S_OK appears in
the status screen.
String voltage is 0V
Power optimizer (s) output is disconnected.
Connect all power optimizer outputs.
String voltage not 0V but lower than number of optimizers
Power optimizer(s) not connected in the string.
Connect all power optimizers
Module(s) not connected properly to power
optimizer inputs (not applicable to smart
modules).
Connect the modules to the optimizer inputs
String reverse polarity.
Check string polarity using a voltmeter and
correct if needed.
Single Phase Inverter with HD-Wave Technology Installation MAN-01-00306-1.1
68
Power Optimizer Troubleshooting