Installation Manual
l Communication gland:Forconnectionofinvertercommunicationoptions.RefertoSettingUp
Communicationonpage52formoreinformation.
l Drain valve:Drainsanymoisturethatmaybeaccumulatedintheunit.
l LCD panel:Displaysinverterinformationandconfigurationparameters
l LCD LEDs:ThreeLEDslocatedtotherightoftheLCDindicatethefollowinginverterstatuses:
Color Description Functionality
Green Power production
On - The inverter is producing power.
Blinking - Standby mode. The inverter is in Standby mode until its
working voltage is reached. The inverter then enters Production
mode and produces power.
Off - The inverter is not producing power. This may be during Night
mode, when the inverter ON/OFF switch is OFF or when an error
occurs.
Yellow
Communication and
inverter shutdown
Blinking:
o
Monitoring information is being received from a power
optimizer.
o
The inverter is being shut down.
Red Fault
On - There is an error. Refer to Errors and Troubleshooting on page
62 for more information.
Blinking - The inverter is being shut down.
All LEDs turn on while the inverter is being configured.
Opening Conduit Drill Guides
Thisstepmaybeperformedbeforeoraftermountingtheinverter.
To open conduit drill guides:
1. MovetheDCSafetyUnitandtheinverterON/OFFswitchtoOFF.
NOTE
When the Safety Switch is OFF (for example during maintenance) it may be locked to prevent safety
hazard:
1. Move the safety switch to the Lock position.
2. Insert the lock through the knob opening and lock.
Single Phase Inverter with HD-Wave Technology Installation MAN-01-00306-1.1
24
Opening Conduit Drill Guides