Installation Manual

Inverter ConfigurationSetup Mode
Afterinverterinstallation,aninstallermayperformbasicsystemconfiguration.Configurationisdone
whentheinverterisinSetupmode.
To enter Setup mode:
1.
TurntheinverterON/OFFswitchtoOFF(ACremainsON).
WARNING!
If the inverter was operating properly (power was produced by the power optimizers), the
following message is displayed.
D C V O L T A G E N O T S A F E
D O N O T D I S C O N N E C T
V D C : 7 2 . 0
This message is displayed until the DC voltage is safe (50V). Do not open the cover until the
voltage is safe or until at least five minutes have passed.
AVERTISSEMENT!
La tension de sécurité par défault est de 50V.
Ne pas ouvrir le couvercle ou les connecteurs DC jusqu'à ce que la tension soit affichée comme
sécurisé ou jusqu'à ce que cinq minutes au moins se soient écoulées.
2. PresstheOKbuttonforatleast5seconds.Thefollowingmessageisdisplayed:
P l e a s e e n t e r
P a s s w o r d
* * * * * * * *
3. PresstheUp, Down and OK buttons(Up=1,Down=2,OK=3)forenteringtheSetupmodepassword:
pq OK pqOK pq(12312312).
TheinverterisnowinSetupmodeandallitsLEDsarelit.TheinverterautomaticallyexitsSetupmodeifno
buttonsarepressedformorethan2minutes.
Thefollowingshowsahierarchicaltreeofthemenuoptions,whicharedescribedinConfigurationMenu
Optionsonpage41.Actualmenusmayvaryfromshowndependingonthefirmwareversionofthe
inverterandonthecountry.
Mainmenu:
Country:
U S A +
Language:
E n g l i s h
G e r m a n
S p a n i s h
F r e n c h
I t a l i a n
Communication:
S e r v e r < L A N >
L A N C o n f
Chapter 5: Configuring the Inverter
Single Phase Inverter with HD-Wave Technology Installation MAN-01-00306-1.1
39