Technical information
12/01/02
Hoshizaki recommends that the ice machine drain and
bin drain be piped separately to the drain connection point
allowing 1/4" per foot fall.
CONDENSATE DRAIN -
The condensate drain is generally connected to the ice
machine drain for simplicity. It can be piped separately to
the drain exit if desired.
A 6" vent tee is recommended as per drawing:
FLOW RATES -
The minimum flow rate requirements for Hoshizaki ice
maker units are as follows:
KM-150/250/280/AII Flakers 1.05 GPM
KM-500 1.58 GPM
KM-630/900/AII DCM's 2.11 GPM
KM-1300/1600 3.96 GPM
KM-2000/2400 4.23 GPM
Use this information when sizing a filter system for the ice
machine application.
NOTE: A good rule of thumb is to utilize a 3 GPM flow rate
filter for KM-150 through 900 and a 5 GPM flow rate filter
for KM-1300 or larger.