Specification Sheet

*Note: Alarm connection contacts close when sensor fails or temperature range is exceeded.
NTC - Negative Temperature Coefficient
PTC - Positive Temperature Coefficient
Note: Sensor type (PTC or NTC) must meet temperature specifications. If averaging, 4 sensors of the same type must be used.
Line Voltage Application
(Non-Power Stealing)
Binary Input
(Gold-Plated
Contacts)
NTC*
Temperature
Sensor
PTC*
Temperature
Sensor
120 VAC
Hot
Neutral
L1
L2
208/240
VAC
Voltage Input
Load
SW2
PTC
BIN
GND
ALARM
NTC
PS
NC
NEUT
LINE
LOA D
24 VAC
TH TR
NON
PS
Alarm Output
For optional connection to
customer alarm equipment
24 VAC
TH - Thermostat Hot
TR - Thermostat Return
Line Voltage Application
(Power Stealing)
VAC Applications
(Non-Power Stealing)
Typical Wiring
Binary Input
(Gold-Plated
Contacts)
NTC*
Temperature
Sensor
PTC*
Temperature
Sensor
120 VAC
Hot
Neutral
L1
L2
208/240
VAC
Voltage Input
Load
Alarm Output
For optional connection to
customer alarm equipment
24 VAC
TH - Thermostat Hot
TR - Thermostat Return
SW2
PTC
BIN
GND
ALARM
NTC
PS
NC
NEUT
LINE
LOA D
24 VAC
TH TR
NON
PS
Binary Input
(Gold-Plated
Contacts)
NTC*
Temperature
Sensor
PTC*
Temperature
Sensor
Load
Alarm Output
For optional connection to
customer alarm equipment
24 VAC
TH - Thermostat Hot
TR - Thermostat Return
SW2
PTC
BIN
GND
ALARM
NTC
PS
NC
NEUT
LINE
LOA D
24 VAC
TH TR
NON
PS
Note: Do not use
Output Relay to control
Line Voltage when
using 24 VAC Power
24 VAC
Class 2
Transformer
Applied voltage: 120 VAC 208 VAC 240 VAC
Full load amps: 16 Amps 9.2 Amps 8 Amps
Locked rotor amps: 96 Amps 55.2 Amps 48 Amps
Non-inductive amps: 16 Amps 16 Amps 16 Amps
Horsepower: 1 hp 1 hp 1 hp
24 VAC: 100 VA, 30 VAC Max. (Class 2)
Pilot duty: 125 VA, 24 to 240 VAC
Minimum load: 1 Amp @ 24 VAC
Load Relay Electrical Ratings
N.C. and Load Contacts (Maximum Load Current)
16E09-101
*
Replaces the Following Models
Danfoss
UT72
Honeywell
T4031A1073
T4031C1004
T4031C1012
T6031A1029
T6054A1005
T6054A1054
T675A1045
T675A1136
T675A1425
T675A1441
T675A1458
T675A1508
T675A1516
T675A1524
T675A1540
T675A1565
T675A1706
T675A1722
T675A1771
T675A1854
T675F1032
T678C1005
T7079A1004
T7079A1012
T7079A1046
T7079A1053
Ranco ETC Commercial
Temperature Controls
060-100
060-101
060-109
060-200
ETC-111000
ETC-112000
Johnson Controls
A19ABA-40C
A19ABC-24C
A19BAB-3C
A19BAC-1C
A19BAF-1C
A19BBC-2C
A319ABC-12-01
A319ABC-24-01
A320ABC-1C
A419ABC-1C
White-Rodgers
1609-33
1609-100
1609-101
1609-102
1609-103
1609-104
1609-105
1687-9
201-8
201-20
230-22
241-2
2A37-1
*16E09-101 is not rated as a limit control
16E09-101 is a replacement on non-inductive applications up to 16 amps
N.O. contacts: 1 Amp (5 to 24 volts AC or DC)
Alarm Relay Electrical Ratings
16E09-101
WR-4975-2
16E09-101
Universal
24/120/208/240 Volts
Universal Replacement
Electronic Refrigeration
or Heating Control
Specifications
Setpoint Range:
-40° to 220°F (-40° to 104°C)
Differential Range: 1° to 30°F (1° to 30°C)
Supply Voltage:
24/120/208/240 VAC, 60Hz
Sensor: Negative Temperature Coefficient
with 7.5-Ft. Leads (Maximum length for
remote temperature sensing – 400 feet)
Control Enclosure Ambient Temperatures
Operating: -29° to 140°F (-34° to 60°C)
Storage: -40° to 185°F (-40° to 85°C)
Control Material
Cover and Case: NEMA 1 high-impact plastic
Thermoplastic: Non-flammable UL94V0
Switch Action: SPDT
Ambient Humidity: 0 to 95% RH, non-condensing
Dimensions
6 3/4" L x 3" W x 2 9/16" D
16E09-101 Optional Accessories/Service Items
Immersion Well: F89-0286
Replacement 7.5-Ft. NTC Remote Sensor: F136-0114
Well Heat Transfer Compound: F145-0650
For Additional Information
Visit www.white-rodgers.com
Alarm Output with Selectable Delay
Prevents false alarms
No Common Wire Required
(Electrical load must be greater than 2.5 amps and uninterrupted)
Saves 30-60 minutes installation time when upgrading a mechanical control
St. Louis, Missouri
314-553-3600
www.white-rodgers.com
www.emerson.com
The Emerson logo is a trademark and
a service mark of Emerson Electric Co.
Size: 8.5" x 11"
Job #:
WRDG_130516
File Name:
130516_16E09_101_ETempCntrl_SS.ai
Printing & Finishing: 4/C Offset
Colors:
CMYK DIE
Printout Size
100%
Updates: jd07.15.10, jd07.19.10,
jd07.28.10, BBpff8.13.10
This printout is for indicating
color breaks only.
Do not use for color matching.
Do not measure for accuracy.
Revision: 04