Brochure

www.white-rodgers.com
141
HYDRONIC
SURFACE (STRAP-ON) TYPES
Attach Directly to Surface of Pipe. Types for use as High Limit,
Reverse Acting or SPDT Switching Action Control.
FEATURES
Sensing element has twice the contact area of competitive models.
Hydraulic action element can be mounted in any position — no leveling required.
Dustproof steel case.
Special screw terminals with “ears” securely hold solid and stranded wires.
Includes pipe strap and mounting screws.
Full Motor Rating Valves and
Model Switch Electrical (Full Load) Relays
Number Range Differential Action Rating 120 VAC 240 VAC 24 VAC 0.3-12v DC
11B02-1 100 to 240°F Fixed 10°F Open on Rise HTV 10.0A 6.0A 6.0A 1.0A
(38 to 116°C) (5.5°C) See page 416
1127-2 100 to 240°F Fixed 10°F SPDT HH 7.4A 3.7A 2.9A
(38 to 116°C) (5.5°C) See page 416
1127-9 60 to 200°F Fixed 15°F SPDT HH 7.4A 3.7A 2.9A
(16 to 93°C) (8°C) See page 416
Has U.L. approved adjustable dial stop, factory set at 220°F maximum.
Has U.L. approved adjustable dial stop, factory set at 150°F maximum.
1127-2
SPDT Contact Structure
HH Rated Controls
Switch Action
R-B Open on Rise
R-W Close on Rise
SPECIFICATIONS
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . 6
7
/
8
H (includes plate) x 2
5
/
16
W x 3
3
/
16
D
Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . Grey
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . U.L. listed and C.S.A. certied
DUAL ACTION – SINGLE ELEMENT CONTROLS
Designed to Replace Any Immersion Type Hot Water Control –
High Limit, Low Limit or High-Low Limit/Circulation Combination
FEATURES
Dual action controls use a single hydraulic action element to operate two precision
snap switches.
Dustproof steel case with top and bottom knockouts and snap-on cover.
Large screw terminals and ample wiring space.
Extra capillary for standard or extended shank well. (Shipped without well. Except
11C30-3)
Motor Rating Valves and
Model Switch (Full Load) Relays
Number Range Differential Action 120 VAC 240 VAC 120 VAC 240 VAC
11C15-11 High Limit: 140 to 240°F (60 to 116°C) Adj. 10 to 35°F Open on Rise 8.0A 6.0A 3.2A 0.25A
Circulator: 100 to 200°F (38 to 93°C) (6 to 19°C) Close on Rise 8.0A 6.0A 3.2A
11C30-3 High Limit: 140 to 240°F (60 to 116°C) Fixed 10°F (6°C) Open on Rise 8.0A 6.0A 0.25A
Low Limit: 140 to 240°F (60 to 116°C) Adj.10 to 35°F (6 to 19°C)
11B54-4 High Limit: 100 to 240°F (45 to 116°C) Fixed 5°F (3°C) Open on Rise 10.0A 6.0A 6.0A 1.0A
Low Limit: 60 to 110°F (16 to 43°C) Fixed 3°F (1.5°C)
11C61-12 High Limit: 140 to 240°F (60 to 116°C) Adj. 10 to 35°F Open on Rise 8.0A 6.0A 0.25A
Low Limit: 100 to 200°F (38 to 93°C) (6 to 19°C) SPDT
11C15-11
SPECIFICATIONS
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . 4
1
/
16
H x 3
3
/
4
W x 2
5
/
16
D
Finish . . . . . . . . . . . . . . . . . . . . . . . . . . . . Grey
Agency . . . . . . . . . . . . . . . . . . . . . . . . . . . U.L. listed and C.S.A. certied
PARTS AND ACCESSORIES See end of this section for additional parts and accessories
F145-0650 – Well adapter and heat conductive compound
F71-0924 – Well adapter only
F145-0163 – Tube heat conductive compound
For immersion wells, see page 147
Terminal
Panel
HYDRONIC
CONTROLS
Indicates Canadian Model Number: call 1-800-305-6953 to order