Owner`s manual

24309-1-0908Page 12

Figure 6a - Mantel Clearances with Standard Hood
Figure 6b - Mantel Clearances with Optional Extended Hood
MANTEL
STANDARD
HOOD
17 ½”
10”
12”
MAX
42”
MIN.
(CEILING TO
TOPOF HOOD)
4½
MIN.
FIREBOX
FACE
84”
MIN.
(CEILING TO FLOOR)
CEILING
COMBUSTIBLES
ALLOWED
3/8” COMBUSTIBLE
CLEARANCE REQUIRED
FROM TOP EDGE
OF FIREPLACE
8”
6½
5”
3½
1½
0”
6½
9”
11
13”
15”
MANTEL
13”
10”
12”
MAX
42”
MIN.
(CEILING TO
TOPOF HOOD)
8”
MIN.
84”
MIN.
(CEILING TO FLOOR)
CEILING
COMBUSTIBLES
ALLOWED
22”
8”
20”
6½
18”
5”
16”
3½
14 ½”
2½
24 ½”
0”
FIREBOX
FACE
EXTENDED HOOD
(VB4H SERIES)
(NOT AVAILABLE ON
PENINSULA OPEN END)
3/8” COMBUSTIBLE
CLEARANCE REQUIRED
FROM TOP EDGE
OF FIREPLACE
Ceiling Clearances: The ceiling height should not be less than 42"
from the top of the hood. See Figures 6a and 6b.
Mantel Clearances: Vent free replace models must use the hood
supplied with the replace, or one of the optional hood kits avail-
able for each model. If a combustible mantel is installed, it must
meet the clearance requirements detailed below.
Leave furniture and other combustible items at least 36" away from
the front openings of the replace.
Do not attach combustible material to the mantel of your replace.
This is a re hazard.
Figure 7
No greeting cards, stockings or ornamentation of any type should
be placed on or attached to the replace. This is a heating appliance.
The ow of heat can ignite combustibles.
Figure 8
COMBUSTIBLE MATERIALS