g GE Security ESL 1500 Series Fire Alarm Control Panel Installation and Operations Manual
Table of Contents Precautions and Warnings ......................................................................... 1 System Overview ......................................................................................... 1 Panel Listing ........................................................................................................................... 1 Panel Description ........................................................................................ 2 Ordering Information ..............
Figures and Tables Figures Figure 1. Internal Panel Configuration .................................................................................... 3 Figure 2. ZEM or LEM Installation ......................................................................................... 4 Figure 3. Window Label Installation ....................................................................................... 4 Figure 4. Template Diagram ................................................................................
Precautions and Warnings The equipment described in this manual is Listed by Underwriters Laboratories, Inc. for use in fire alarm signaling systems, only when installed in accordance with this manual and National Fire Protection Association’s National Fire Alarm Code (NFPA 72); the National Electrical Code (NFPA 70); the Life Safety Code (NFPA 101); and the local authority having jurisdiction (AHJ). The installer must be familiar with and understand all applicable codes before beginning installation.
Panel Description Standard Features: Optional Features: • • • • • • • • • • • • Modular design; 1, 3, or 5 zones Power limited 1.5 Amp. 24 VDC FWR output Local Energy Module (LEM) Zone Relay Module (ZRM) 5 relays Remote Annunciators (RA) All functions DIP switch activated Built-in walktest and alarm verification Sprinkler supervisory and waterflow alarm activation Class A (Style D) or Class B (Style B) initiating wiring Reliability of surface-mount design Superior lightning protection Table 1.
Installing the Panel To install the unit, follow these 12 steps, and refer to the proper sections for more information. 1. Create System Diagram: Prepare a carefully laid out drawing of the complete wiring system hookup. Maintain this drawing as a permanent record of the system application and include any future modifications. Note: “As-built” drawings and this manual should be available at all times to verify agreement between the connected equipment and the drawings. 2.
Optional Zone Expansion and Communicator Module Installation 24 VAC AC IN Z1RA– SYSTEM COM NO +15VDC CASE Z1B+ Z1A+ Z1A– Z1B– AUX SYS FIRE GROUND 24VFWR GND DRILL ZONE 1 NC COM TROUBLE RELAY ZONE NC NO B– ALARM RELAY B+ 1 TROUBLE SUPERVISORY INDICATING LOW/NO AC POWER 1 LOW/ NO BATTERY GROUND FAULT SENTROL, INC. 10831 SW Boulevard 12345 SW Cascade Leveton Dr.
Optional Remote Notification Disconnect Applies to LEM optional module. Disconnects system from remote sites. When activated, the trip circuit fault LED and system fault condition will exist and remain until the switch is returned to the normal position. Note: Notify the local fire department and the receiving station before disconnecting the LEM from the system. Table 2. Status Indicators Indicator Normal Color Description AC Power On Green Indicates main power is operating from AC power source.
Z1RA– SYSTEM COM NO +15VDC CASE Z1B+ Z1A+ Z1A– Z1B– AUX SYS FIRE 24VFWR GND DRILL GROUND 24 VAC AC IN ZONE 1 NC COM TROUBLE RELAY ZONE NC NO B– ALARM RELAY B+ 1 TROUBLE SUPERVISORY LOW/NO AC POWER 1 LOW/NO BATTERY B– INDICATING 1 TROUBLE INDICATING 2 TROUBLE NORMAL WALKTEST ZONE 1 POWER LIMITED 24 VDC BATTERY IN 2 A– DISCONNECT 2 DISCONNECT WALKTEST Z2B+ Z2A+ Z2A- A+ NORMAL NORMAL AC POWER DISCONNECT TRBL ALARM TRBL NORMAL NORMAL B+ INDICATING SYSTEM ZONE A– GROUND FAU
Field Wiring Class A System Wiring Diagram 204-12/24V Power supervision relay Zone 1 is shown with 4-wire detectors, wired in Class A (Style D) + + 449C Bell circuit 1 is shown with Class A (Style Z) wiring Local Zone 1 alarm (Supervised) Connect to 120 V AC Blk Wht 60Hz + + - System 15VDC System trouble Auxiliary alarm contacts contacts Connector from transformer B+ A+ 1 A- B- 6 7 9 8 10 11 12 13 14 15 16 C N/O N/C C N/C N/O Power ON (standby condition) Auxiliary power(+) Case ground BM
Class B System Wiring Diagram 204-12/24V Power supervision relay 2.7K EOL Resistor 1/2W Zone 1 is shown with 4-wire detectors, wired in Class B (Style B) + + 449C 541C 2.
Table 3. Wire Resistance 3 2 1 2 1 3 5 4 6 7 8 9 10 11 12 13 14 Gauge 17 15 16 9 18 19 ESL 1500 Series Fire Alarm Control Panel 4 20 21 22 23 24 8 1 2 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 5 Ohms per 1000 ft. @ 20°C of single conductor copper wire 12 1.6 14 2.5 16 4.0 18 6.4 20 10.0 22 16.0 9 10 7 6 Table 4. Alarm Indicating Circuit Wire Size 1. Case ground 2. Power limited Zone 1 and Remote Annunciator 3.
Do not overlook adequate lightning protection. Lightning damage commonly occurs from three sources: 1. Through alarm loop wiring 2. Through AC power inputs 3. Through earth ground or power ground connections The 1500 System has substantial lightning protection incorporated in all three areas. However, proper lightning protection for AC power must be accomplished where the wire enters the building.
Sprinkler System Waterflow and Supervisory Devices Normally open contact type waterflow alarm devices may be connected, along with conventional manual alarm stations or heat detectors. All zones to which waterflow alarm devices are connected may be programmed so that the system alarm indicating devices cannot be silenced. See Programming. Supervisory signals for status reporting of waterflow control valves, supplies, etc. must be connected to a separate zone, and programmed for supervisory status.
1 2 Zone #1 trouble Supervisory Low/no AC Low/no battery Ground fault Indicating #1 trouble Indicating #2 trouble ON 3 1 2 3 4 5 6 7 8 10 4 TB1 System+15 VDC of BMB To Z1RA-of BMB (Zone) COM COIL N/O C N/C COIL N/P C N/C COIL N/O C N/C COIL N/O C N/C COIL N/O C N/C 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 To Z2RA-of ZEM (Zone 2) To Z3RA-of ZEM (Zone 3) To Z4RA-of ZEM (Zone 4) To Z5RA-of ZEM (Zone 5) 9 K1 5 D6 D1 K2 D2 8 K3 K4 D4 K5 D5 1. Mounting hole 2.
Connecting Optional Remote Notification Devices 1500-RA-5A Note: When using remote annunciators other than the ESL 1500-RA-5A, be sure all circuits have a series resistance of at least 1K ohm. Maximum current should be 15mA per zone. The control unit can properly power one remote annunciator. When a remote annunciator is used, both the BMB and ZEM must be programmed to provide supervision. See Programming.
Programming BMB Programming All programming selections are controlled by switches located in the lower right corner of the BMB. Table 5 shows default (factory) prgramming along with a description of each feature. Table 5. BMB Programming Features Switch Factory # Position Feature Description 8,7,6 off not used not used 5 off zone 2 supervisory Disables fire alarm signal and provides distinctive audible and visual supervisory signals. Must also program ZEM zone 2 switches 3, 4, 5, & 6.
Testing and System Checkout Following installation and programming of the unit, a complete test of the entire system must be conducted to assure proper operation. NFPA 72, National Fire Alarm Code should serve as the guide. Follow the recommended procedures, restoring all switches and wiring to normal before proceeding to the next step. Notify all building personnel and the fire department and monitoring facilities before and after system testing.
Troubleshooting Table 7 provides a quick reference troubleshooting guide that will aide in diagnosing and locating most system faults quickly and efficiently. If you cannot resolve the fault with the assistance of this guide, call Technical Support at 800.648.7424. Table 7.
Specifications General Remote indicator Operating temperature........................ 0° to 49°C (32° to 120°F) Voltage ........................................................................ 12 VDC Housing Current ................................................................. 15 mA max. Type............................Steel with hinged/removable, locking door Size..........14.0 in. x 14.0 in. x 4.5 in.(35.6cm x 35.6cm x 11.4cm) Finish..................................................
Appendix A, Compatible Equipment The equipment listed here is compatible with the ESL 1500 Series Fire Control Panel. Use ONLY UL Listed compatible quipment with the 1500 Series to assure proper operation. Should you have any questions about compatibility, call technical support at 800.648.7424. Initiating Devices Table 8. Compatible Indicating Devices Compatible Equipment: • • • • 18 Manufacturer Part Number Amseco SLB24-75C Amseco SLB24G-75C Compatible indicating devices shown in Table 8.
Table 9.
Appendix B ESL 1500 Series Standby Battery Power Worksheet 1500 Series System Components Standby Current Per Device Total Standby Current Alarm Current Per Device Total Alarm Current 1500-BMB (Zone 1) 100 mA Indicating Circuit #1 5 mA 1 Amp = 1000 mA mA Indicating Cicuit #2 5 mA 1 Amp = 1000 mA mA mA 1 Amp = 1000 mA mA Auxiliary System Power 200 mA 1500-ZEM (Zone 2) 8 mA mA 70 mA mA 1500-ZEM (Zone 3) 8 mA mA 70 mA mA 1500-ZEM (Zone 4) 8 mA mA 70 mA mA 1500-ZEM (Zone 5) 8
Appendix C 1500 Series Operating Instructions Refer to the 1500 Series Installation Manual for more information Normal Standby Condition Trouble Condition • Green “AX POWER” LED “ON” • Yellow system trouble LED is “ON” • All other LEDs “OFF” • Yellow diagnostic LED is “ON” • All switches in “NORMAL” position • Integral sounder sounds a slow intermittent signal Alarm Condition • System trouble relay contacts transfer • Red local zone alarm LED “ON” Sounder Silence Switch Operated • Integral sound
g GE Security GE Security 12345 SW Leveton Drive Tualatin, OR 97062 503-692-4052 USA & Canada: 800-547-2556 Tech Support 800-648-7424 FaxBack: 800-483-2495 www.GESecurity.com 12603 Rev. J 04/04 64812687 Rev.