Technical data
Chapter 11: Battery Backup Calculation Worksheet
SP40S BATTERY CALCULATION SHEET
STANBY CURRENT CALCULATIONS
1. The Standby Current for the SP40S is 0.130 Amps. ______________Amps
2. Enter Auxiliary Current (If Applicable) ______________Amps
3. Add Steps 1 and 2. Multiply by the number of hours required.
24 Hours – Multiply by 24 ______________Hrs
TOTAL STANDBY CAPACITY IN AMP HOURS ______________Ah
ALARM CURRENT CALCULATIONS
NOTE: DO NOT EXCEED 40 WATTS.
Good engineering practices call for amplifier to operate at 85% Max wattage.
1. List the speaker and strobe requirements.
NOTIFICATION
APPLIANCE
SPEAKER
WATTAGE
STROBE
CURRENT
2. Calculate total Strobe current. (2. Amps Max.) ______________Amps
3. Calculate total speaker wattage. (40 Watts Max.) ____________
4. Multiply the total speaker wattage on line 3 by 0.054. ______________Amps
5 Add Auxiliary Current (if applicable) ______________Amps
6. Add Steps 2,4 and 5 together. (4.66 Amps Max.) ______________Amps
7. Multiply Step 6 by 0.25 (This represents 15 minutes of alarm.) ______________ Hrs
8 Total Alarm Capacity in Amps-Hours. ______________ Ah
BACKUP BATTERY REQUIREMENS
1. Enter Standby Capacity. ______________ Ah
2. Enter Alarm Capacity. ______________ Ah
3. Add Steps 1 and 2 together. ______________ Ah
Multiply Step 3 by 1.1 for minimum Backup Battery Requirements ______________Ah
NOTE: THE UL LISTED BACKUP BATTERIES FOR THIS PANEL ARE TWO 12 VOLT,
12 Ah.
SP40S Multi-Function Facility Communication System Manual, Revision D
2